The glass bulb
A small glass bulb holds a plug in the head. The liquid inside expands with heat; at the rated temperature the bulb shatters and water flows.
WhyHeads open one at a time, where the heat is. Movies are wrong: a kitchen fire does not set off every sprinkler in the house.
Quick response
Residential heads are quick-response and spray high on the walls to keep a room survivable while people get out.
The piping
Residential systems use CPVC, PEX or copper, often fed from the house supply. Some are multipurpose, sharing pipe with the plumbing so water moves through them every day.
Roof and vents
A Class A roof resists burning embers landing on it. Attic and crawlspace vents are where embers get inside, so vents in fire zones must resist ember and flame intrusion.
Eaves, glass and walls
Enclosed eaves remove the pockets where heat and embers collect. Tempered glass resists breaking in radiant heat. Stucco, a South Coast staple, is noncombustible.
Gutters and the first five feet
Dry leaves in gutters and bark mulch against walls catch embers. Fire agencies urge a noncombustible zone in the first five feet around the house.
Five stations
Frames are machined from brass, glass bulbs are filled with a liquid calibrated to burst at a set temperature, heads are assembled and loaded, and each is pressure-tested.
Color means temperature
Bulb color marks the operating temperature: orange and red bulbs are the ordinary ratings used in most rooms; hotter ratings go near heat sources.
Water supply
Sprinkler flow can exceed a typical house meter, so the water district may require a larger meter or service. It is one of the first things to check on a new house or ADU.
Coverage and spacing
Heads are spaced by their listing to cover each room, with attention to sloped ceilings, beams and soffits that can block the spray.
Inspection
The fire department reviews the design and inspects the rough piping and the final system.
Santa Barbara: Montecito is served by the Montecito Fire Protection District; most of the City of Santa Barbara by the City fire department; unincorporated areas by County Fire.
Chapter 5 of 7
A century of fire on the South Coast.
Each major fire left something in the code.
1964: the Coyote Fire
The Coyote Fire burned through the Santa Barbara and Montecito foothills, one of several mid-century fires in the front country.
1990: the Painted Cave Fire
Driven by sundowner winds, the Painted Cave Fire burned more than 400 homes in a few hours, and local building standards tightened afterward.
2008: Chapter 7A
California’s wildland-urban interface building standards took effect: roofs, vents, eaves, glass, decks and siding in fire hazard zones. The Tea Fire burned Montecito homes that November.
2011: sprinklers in new homes
From 1 January 2011, California required automatic fire sprinklers in all new one- and two-family homes.
2017 and 2018
The Thomas Fire burned the hills above Montecito in December 2017; the burned slopes fed the debris flows of 9 January 2018.
Today
Class A roofs, ember-resistant vents, tempered glass, enclosed eaves, sprinklers inside, and defensible space outside.
Chapter 6 of 7
The same trade, on a real ADU.
Every course ends on one building: a 710-square-foot ADU on Canon Drive in the Santa Barbara foothills, modelled from its permit set before pricing. Three gables, three floor levels, a steel canopy, and a list of questions the drawings left open. Here is a foothill ADU checked against the high fire rules.
Wood cladding needs a fire listing
The City's high fire standards call for exterior walls that are noncombustible or ignition-resistant from foundation to roof, and they do not allow ordinary wood siding over gypsum. Submittal 3 names Thermory Kodiak spruce, a heat-treated wood, but cites no fire listing. It needs one, or an assembly that complies, before it can be priced firm.
WhyOne option: a noncombustible plank that looks like wood. Switch the cladding in the model to see it.
A plank that looks like wood
Here is the same building with a noncombustible plank in place of the wood. The architecture stays the same; the material behind it changes.
Sprinklers, now on the plans
Submittal 3 makes the ADU sprinklered, to NFPA 13D under its own permit. The system adds a riser in the water-heater closet and a head in every room, with piping hidden in vaulted ceilings, and the existing 5/8-inch meter is shown as enough at 20 gallons a minute.
Vents, eaves and glass
Ember-resistant vents or 1/8-inch metal mesh, noncombustible eave undersides, a tempered pane in every window, and exterior doors that are noncombustible, 20-minute rated or at least 1-3/8 inch solid core.
Vents and eaves
Replacing attic and crawlspace vents with ember-resistant ones is one of the most effective, least expensive upgrades.
Gutters, decks and the first five feet
Metal gutters with guards, noncombustible decking near the house, and gravel or pavers in the first five feet keep embers from finding fuel.
Decks in fire country
A deck is a shelf for embers. In high fire hazard zones the decking must be ignition-resistant or noncombustible, posts metal or heavy timber, the space underneath kept clear of stored things and planted with nothing that burns, and the joint where the deck meets the house flashed so embers cannot lodge against the wall.
WhyLeaves and debris between deck boards and the wall are where many houses ignite. Gaps are kept clean as part of yearly maintenance.
Sprinklers in additions and ADUs
New homes and many accessory dwellings need sprinklers; additions to a sprinklered house extend the system. Local rules vary, so we check early.
Can the fire engine get there?
In the hills the fire department reviews access before anything else: a driveway wide and strong enough for an engine, grades it can climb, a turnaround where the drive is long, a hydrant close enough with enough flow, and an address sign readable from the road at night.
WhyAccess requirements can set the whole site plan on a steep lot, and they are checked before the house design is approved.
The riser: where sprinklers start
A home sprinkler system starts at the water meter, sized for the house and the sprinklers together. Where the water purveyor requires it, a backflow device keeps sprinkler water out of the drinking water. Inside, the riser carries a control valve, a flow switch that sounds an alarm when a head opens, a test and drain valve, and an outside bell.
WhyAn undersized meter or a long, narrow service is the most common reason a sprinkler design fails its calculation. Meter size is checked before the house is designed, not after.
Ember-resistant vents
Most houses that burn in a wildfire are lit by embers, not by the flame front, and attic and crawlspace vents are a main way in. In the state's wildfire zones the building code asks that vents keep embers out: either a noncombustible, corrosion-resistant mesh with openings between one-sixteenth and one-eighth of an inch, or a vent listed to the ASTM E2886 test for ember and flame intrusion. Finer mesh clogs and starves the attic of air, which is why the listed vents exist.
WhyA vent with the wrong mesh is a failed inspection and a weak point in the house. Check the listing on the submittal.
Santa Barbara: Much of Montecito, the Riviera, Mission Canyon and the foothills are in Very High Fire Hazard Severity Zones.
The garage door
A garage is full of fuel, cars, paint, cardboard, and its big door is often the leakiest opening in the house. In California's wildfire zones the building code asks that a garage door resist ember intrusion: the gaps at the sides, head and bottom held to about an eighth of an inch with weatherstripping, brush seals or a bottom seal. Old doors that have sagged usually fail. Adjusting the door and replacing worn seals is one of the cheapest hardening jobs there is.
WhyCheck the garage door gaps with a flashlight at night from inside; any light you see, embers can use.
Never paint a sprinkler head
A sprinkler head works because a small glass bulb or fusible link breaks at a set temperature. Paint, texture or overspray on it can slow or stop that response and block the deflector. Heads are covered with the bag or cap they ship with, or carefully masked, before any painting or ceiling texture, and the covers come off before the final. A painted head is not cleaned; it is replaced by the sprinkler contractor.
WhyAssign one person to remove every sprinkler cover before the final inspection. Inspectors check.