Heating, cooling and ventilation. Moving heat, not making it.

A heat pump does not burn anything: it moves heat from outside to inside in winter and the other way in summer. This course opens one up, follows the air through the ducts, shows how fresh air gets into a tight house, and walks a century of South Coast heating, from floor furnaces to the heat-pump baseline of the 2025 code.

7 chapters37 3D scenes10 min readSanta Barbara South CoastChecked 19 Nov 2026

The 3D scenes need WebGL, which this browser has turned off. Every word of the course is still here on the left.

Chapter 1 of 7

How a heat pump moves heat.

A heat pump is a refrigerator turned to face the house. Refrigerant carries heat around a loop.

The loop

Refrigerant is pumped around a closed loop between an outdoor coil and an indoor coil. Where it evaporates, it absorbs heat; where it condenses, it releases heat.

WhyMoving heat takes far less electricity than making it. A heat pump can deliver several units of heat for each unit of electricity.

Reverse it for cooling

A reversing valve swaps the roles of the two coils, so the same machine heats in winter and cools in summer.

Indoors: the air handler

A fan pulls house air through a filter and across the indoor coil, then pushes it through supply ducts to the rooms; return ducts bring it back.

Chapter 2 of 7

Every system you will find here.

The mild South Coast climate produced an unusual mix of heating systems.

Floor furnaces and wall heaters

Many South Coast houses from the 1920s to the 1960s were heated by a gas floor furnace in the hallway or wall heaters in a few rooms, with no ducts and no air conditioning.

WhyOld floor furnaces and wall heaters are worth a safety check: cracked heat exchangers and poor venting can leak carbon monoxide.

Forced air

A furnace or heat pump with ducts to every room. Common from the 1960s on, often in the attic or crawlspace.

Ductless and radiant

Mini-splits mount a small head in each room and need no ducts, which suits older houses. Radiant floors circulate warm water in tubing under the floor.

Fresh air

An energy or heat recovery ventilator brings in outdoor air and exhausts stale air, swapping heat between the streams.

WhyTighter houses need deliberate ventilation; California requires whole-house mechanical ventilation in new homes.

Chapter 3 of 7

From a steel coil to a duct run.

Sheet-metal duct is rolled, seamed and insulated in a shop, then fitted on site.

Six stations

Galvanized coil is sheared, rolled into round or rectangular duct, seamed, formed into elbows and boots, and wrapped in insulation for runs through attics.

Flex duct

Flexible duct is a wire helix in plastic film, wrapped in insulation and a vapor jacket. It is quick to install and loses airflow when kinked or sagging.

Chapter 4 of 7

Done right: size it, seal it, test it.

Most comfort complaints trace to sizing and ducts, not the equipment.

Size from a load calculation

Equipment is sized from a room-by-room heat load calculation, not from the old unit’s label. Oversized units short-cycle, dehumidify poorly and wear out sooner.

Seal and test the ducts

Every joint is sealed with mastic or listed tape, and new or altered systems are leak-tested by a HERS rater under California’s energy code.

Commission it

Gauges on the line set confirm the refrigerant charge, airflow is measured at the coil, and the owner is shown the filter and the controls.

Chapter 5 of 7

A hundred years of South Coast comfort.

For most of the century, many houses here had no cooling at all, and a single heater.

1920s: fireplaces

Spanish Colonial Revival houses relied on fireplaces and, sometimes, a basement gravity furnace.

1940s: the floor furnace

A gas floor furnace under a hallway grille heated many modest houses: one hot spot, no ducts.

1960s: forced air

Furnaces with attic ducts spread through tract houses; ducts were rarely sealed.

1990s: air conditioning

Central air conditioning became more common as inland heat waves reached the coast.

2026: heat pumps by default

The 2025 Energy Code, effective 1 January 2026, sets heat pumps for space and water heating as the baseline for new homes. Gas designs must make up the difference elsewhere.

Chapter 6 of 7

The same trade, on a real ADU.

Every course ends on one building: a 710-square-foot ADU on Canon Drive in the Santa Barbara foothills, modelled from its permit set before pricing. Three gables, three floor levels, a steel canopy, and a list of questions the drawings left open. Here is heating, cooling and fresh air in 710 square feet.

Three heads, one outdoor unit

The proposed layout has a ductless head in the living room, the bedroom and the primary, all on one three-zone outdoor unit on a pad north of the bath. Final sizing comes from the mechanical engineer's load calculation.

Line sets outside the wall

The line sets leave each head through the north wall and run in a painted cover down to the outdoor unit, never across a window or a door.

160 cfm, not 100

For a home under 750 square feet with an electric range, the 2022 Energy Code calls for a range hood rated 160 cfm or 65 percent capture efficiency. This ADU is 710 square feet; an earlier version of our model said 100 cfm, and we corrected it.

Two bath fans

Each bathroom gets an ENERGY STAR fan with humidity control, ducted to an ember-resistant roof jack. The fans and the hood were required but not drawn, so we located them.

Chapter 7 of 7

What it means for your house.

Heating and cooling choices depend on whether you are opening walls and ceilings.

Replace a furnace with a heat pump

In a house with ducts, a ducted heat pump can replace the furnace and add cooling. The ducts are tested, sealed, and often replaced if they are old flex duct.

No ducts? Go ductless

Older houses without ducts are good candidates for mini-splits: small heads in key rooms, one outdoor unit, no walls torn open.

A ductless install

A mini-split puts a head high on an inside wall (seen here from inside the room) and an outdoor unit on a pad or bracket just outside. Between them runs a line set: two refrigerant lines, a power cable and a condensate drain, through one small hole and up the outside wall in a painted cover. The drain runs to daylight or a small pump.

WhyOn a historic front wall a line-set cover is a design review item. Route it on a side or rear wall, or inside a closet.

Ventilation you can see

A tight house needs planned air: a balanced ventilator (an ERV or HRV) brings fresh air in and sends stale air out, trading heat between the two streams; the range hood and every bath fan are ducted all the way outside, not into the attic. California requires whole-house ventilation in new homes and a hood that vents outdoors.

WhyA gas range without a ducted hood is the biggest indoor air problem in many kitchens. In a remodel, the hood duct route is planned with the cabinets.

Radiant floors, up close

Radiant heat runs warm water through loops of PEX tubing laid over insulation and buried in a thin pour or set in grooved panels. Each loop starts and ends at a manifold, and a heat pump or boiler heats the water to well under bath temperature. Tile or engineered wood goes on top; thick carpet works against it.

WhyRadiant is slow to warm and slow to cool, so it is set and left alone. It pairs well with a heat pump water heater and with the tile floors common in Spanish Colonial Revival houses.

Electrical capacity

Heat pumps, heat-pump water heaters and induction cooking can push an older 100-amp service past its limit; a load calculation decides. The Cannon Drive ADU takes its power as a feeder from the main house; the feeder route and panel size are still open questions on its plans.

Air has to get back

Every room that gets supply air needs a way for it to return. In a house with one central return in the hall, a bedroom with its door shut fills up with air and the supply slows; a jumper duct or transfer grille over the door lets it flow back. Good duct design sizes returns as carefully as supplies.

WhyA bedroom that is always stuffy with the door closed, or a door that whistles, is usually a missing return path.

Filters and smoke days

Wildfire smoke reaches every South Coast house some years. A MERV 13 filter catches most fine smoke particles, but it resists airflow, so the filter slot is sized for it, ideally a deep media filter, and the fan set to run. Portable HEPA cleaners in bedrooms fill the gap in houses without ducts.

WhyA thick filter jammed into a slot made for a thin one starves the system of air. Size the filter rack when the duct system is designed.

Thermostats and zones

One thermostat in the hall cannot keep a sunny addition, a shaded bedroom wing and an upstairs all comfortable. Zoning splits the house: each zone has its own thermostat, and dampers in the ducts or separate ductless heads deliver heat or cooling only where it is called for.

WhyMost comfort complaints in remodeled houses come from new rooms added to an old system with one thermostat. Zones are planned with the duct design.

Big range hoods need make-up air

A professional range hood can pull many hundreds of cubic feet of air a minute out of a tight house. The residential code requires make-up air for any kitchen hood able to exhaust more than 400 cfm: a duct with a motorized damper, often with its own heater or tempering, interlocked so it opens when the hood runs. Without it the hood starves, doors whistle, and a fireplace or gas appliance can be drawn backward into the room.

WhyThe hood is chosen by the designer and the make-up air by the mechanical engineer. One of them has to tell the other.

Wine rooms

Wine keeps best cool and steady, around 55 degrees and fairly humid. A wine room is built like a small refrigerator: a vapor barrier on the warm side of every wall and the ceiling, thick insulation, an exterior-grade door with weatherstripping, and a cooling unit made for cellars, which works at those temperatures without drying the air. Ordinary air conditioning is the wrong tool; it runs too warm and too dry.

WhyThe vapor barrier is the step that gets missed. Without it, the cold room pulls moisture into its own walls.

Humidity for art, wood and instruments

Paintings on wood panel, antique furniture, wood floors and pianos all swell and shrink with humidity. On the coast the air is damp most of the year and very dry on Santa Ana or sundowner days. Rooms that hold collections get humidity sensors and a system that can add or remove moisture, sized by the mechanical engineer, not only a thermostat.

WhyA stable 40 to 55 percent relative humidity protects floors and casework as much as art. Ask the collector what range their conservator wants.

Pull a vacuum

A heat pump or air conditioner is a sealed loop, and it is only as good as the day it was sealed. The installer brazes the copper line set while flowing nitrogen through it so no scale forms inside, pressure-tests the joints, then pulls a deep vacuum with a pump and a micron gauge to boil off moisture and air. A common target is 500 microns, and the gauge has to hold near that after the pump is valved off; if it climbs, there is a leak or moisture. Only then is the refrigerant released.

WhyMoisture left in a system turns to acid and kills compressors years later. Ask to see the micron reading, not just "it's cold".

J, S and D

Good heating and cooling is designed in three steps that come from the industry's ACCA manuals. Manual J calculates the heating and cooling load room by room from the walls, windows, orientation and climate. Manual S picks equipment sized to that load, not to the old unit or a rule of thumb. Manual D sizes the ducts and registers so each room gets its share of air at a pressure the equipment can deliver. Oversized equipment short-cycles, dehumidifies poorly and is noisy.

WhyOn the mild South Coast oversizing is the common mistake. Ask for the Manual J before anyone quotes a tonnage.

Condensate goes somewhere

An air conditioner or heat pump pulls water out of the air, gallons a day in humid weather, and that condensate has to drain. The primary drain is trapped, sloped and run to an approved place. Where the unit sits over a finished ceiling, as in an attic, the mechanical code asks for a backup: a secondary pan with its own drain to a visible spot, or a float switch that shuts the unit off when water rises. A clogged drain with no backup is a stained ceiling.

WhyIf water drips from the secondary drain outlet, the primary is blocked. Tell the owner what that drip means.

Fans go outside

A bath or laundry fan moves wet air, and the code requires it to discharge outdoors, through a duct to a roof or wall cap with a backdraft damper. Fans that blow into the attic, or ducts that end near a soffit vent and blow back in, soak the insulation and grow mold on the roof sheathing. The duct should be as short and straight as practical, insulated where it crosses a cold attic, and sized as the fan maker asks.

WhyCheck every fan duct in the attic before insulation. A disconnected one is easy to fix now and expensive later.

After the film

Use it on a real house.

On your house

For most South Coast remodels, a heat pump is the natural replacement for an old furnace or floor heater, and adds cooling for the hot weeks.

For our crew

The AMN crew trains on the full private set for this trade: a 3D job site you walk station by station, the lesson plan, the field guide, the math and the tools. Sign-in is not needed, but these pages are kept out of search.

Trades in this course

  • HVAC (heating and cooling) · C-20
  • Radiant floor heating · C-4
  • Ventilation and air quality · C-20

All 100 trades

Before you hire

In California, a license is needed for any job of $1,000 or more in labor and materials, any job that needs a permit, or any job where the worker hires help. Look up the contractor’s license number at cslb.ca.gov and check it is active and carries the right class:

  • HVAC (heating and cooling): CSLB class C-20
  • Radiant floor heating: CSLB class C-4

On the job: the install checklist.

The install chapter as a list to walk before you call the work done. Ticks stay in this browser only. Prints on one page.

Heating, cooling and ventilation · Job: ________________ · Date: __________ · Checked by: ________________

Check yourself. Out loud.

The same drill our crew uses: give the answer in two sentences before you open each one. If you can only name the thing, read that chapter again.

01 The loopSay why it matters, then open

Moving heat takes far less electricity than making it. A heat pump can deliver several units of heat for each unit of electricity.

From chapter: Inside a heat pump

02 Fresh airSay why it matters, then open

Tighter houses need deliberate ventilation; California requires whole-house mechanical ventilation in new homes.

From chapter: Kinds of system

03 Radiant floors, up closeSay why it matters, then open

Radiant is slow to warm and slow to cool, so it is set and left alone. It pairs well with a heat pump water heater and with the tile floors common in Spanish Colonial Revival houses.

From chapter: Your house

04 Thermostats and zonesSay why it matters, then open

Most comfort complaints in remodeled houses come from new rooms added to an old system with one thermostat. Zones are planned with the duct design.

From chapter: Your house

05 Wine roomsSay why it matters, then open

The vapor barrier is the step that gets missed. Without it, the cold room pulls moisture into its own walls.

From chapter: Your house

06 J, S and DSay why it matters, then open

On the mild South Coast oversizing is the common mistake. Ask for the Manual J before anyone quotes a tonnage.

From chapter: Your house

Words in this course.

9 terms in plain English, with the Spanish our crew uses. All 249 words across the school are on one page.

Heat pump Bomba de calor
An electric machine that both heats and cools a house by moving heat, not making it.
Make-up air Aire de reposición
Outdoor air brought in to replace what a large exhaust fan takes out.
Manual J Manual J
The industry method for calculating a house's heating and cooling load room by room.
Micron gauge Vacuómetro de micrones
A gauge that measures the deep vacuum pulled on a refrigerant line set.
Radiant floor Piso radiante
Heating from warm-water tubes under the floor.
Relative humidity Humedad relativa
How much water vapor the air holds compared with the most it could hold.
Sheathing Entablado
The plywood skin nailed over the wall and roof framing.
Soffit Sofito
The underside of a roof overhang, a beam or an arch.
Spanish Colonial Revival Spanish Colonial Revival
The white-plaster, red-tile style that defines Santa Barbara, built mostly 1915 to 1930.

Questions people ask.

What is a heat pump?

An electric system that moves heat instead of making it: from outdoors to indoors in winter and the reverse in summer. It heats and cools with one machine.

Do I need air conditioning in Santa Barbara?

Many coastal houses did without it for decades. Hotter summers have made it more common; a heat pump adds cooling while replacing the heating system.

Are floor furnaces safe?

Old floor furnaces and wall heaters can work for decades, but cracked heat exchangers and poor venting can leak carbon monoxide. Have them inspected, and install CO alarms.

Does California require heat pumps?

The 2025 Energy Code, effective 1 January 2026, uses heat pumps for space and water heating as the baseline for new homes. Gas is not banned, but gas designs must make up the efficiency difference elsewhere.

What is a Manual J?

An industry-standard room-by-room calculation of how much heat a house gains and loses. Manual S then sizes the equipment to it and Manual D sizes the ducts.

Does a big range hood need make-up air?

Yes. The residential code requires make-up air for any kitchen hood able to exhaust more than 400 cfm: a duct with a motorized damper, interlocked so it opens when the hood runs. Without it the hood starves and can pull a fireplace or gas appliance backward.

Can a wine room use ordinary air conditioning?

No. Wine wants about 55 degrees and fairly humid air; ordinary air conditioning runs too warm and too dry. A wine room is built like a refrigerator, with a vapor barrier on the warm side, thick insulation, a sealed door and a cooling unit made for cellars.

Sources and checks

Rules change with each code cycle, and the plans, the inspector, the adopted code and the maker’s instructions overrule any course. Code references are to the 2025 California Building Standards Code (Title 24), in force since 1 January 2026; check the local amendments of the city or county. This page was checked against these on 18 November 2026:

  • California Energy Commission, 2025 Energy Code (heat-pump baseline; effective 1 January 2026)
  • Title 24 Part 6 duct sealing and HERS verification requirements; ASHRAE 62.2 whole-house ventilation
  • ACCA Manual J (load calculation) and Manual D (duct design)
  • California Mechanical Code
  • AMN crew field guide: Heating, cooling and ventilation
  • ACCA Manuals J, S and D
  • California Mechanical and Residential Codes: exhaust discharged to the outdoors
  • California Residential Code M1503 (kitchen exhaust; make-up air above 400 cfm)