← Heating, cooling and ventilation lesson planCrew training glossaryEspañol

The Complete Guide to Residential HVAC

Oct 27, 2026

As of 2026-10-28. Facts come from the research files and fetched pages in the source ledger. Anything unconfirmed reads "typical value, check the manufacturer manual or code". What changed: the guide now has drawn exhibits, such as the refrigerant loop, the split-system map, the furnace ignition sequence, thermostat wiring, no-cool and no-heat decision trees, the Manual J to S to D workflow, a pressure chart, the system choice flow, the duct loop, the A2L leak response and the startup order. It also has a Day 1 to master course, a safety table, one numbered installation list, a glossary and a table of what a master checks first. Every section links to the exact 3D scene it pairs with. Twelve new sections cover heat pumps, mini-splits, thermostats, ventilation, water heaters, venting and gas leaks, ductwork, A2L leak sensors, coastal heat, customers and warranty, rebates and careers. Corrections: the CO alarm statute is Health and Safety Code 17926, 91 FR 31284 supersedes the R-410A install cutoff, and the $627 furnace permit is a City of Santa Barbara figure, not a Montecito one. A 2026-10-28 audit fixed the rule-of-thumb overshoot (82% to 118% over the load), the 0.68 constant (1060 BTU/lb), the R-454B and R-22 pressure comparisons and the leak-repair exemption for residential equipment. It also linked the status chips to their sources. The 2026-10-28 local pass adds the section Montecito and Santa Barbara: your local rules (agency by address, County permits and fees, design review, Coastal Zone, noise, fire, flood, climate zone, utilities and open items), labels every City-only figure, and applies the local rules in the Installation, Diagnostics, Tools, Code, Business and Coastal sections.

Start here

Residential HVAC moves heat: out of a house in summer, into it in winter, and keeps the air clean and dry enough to live in. Every job comes down to three things, airflow, refrigerant and combustion or electricity, and a master checks them in that order.

How a master thinks. Measure before touching. Airflow problems cause most "refrigerant" complaints, so check filter, coil and static pressure first. Change one thing at a time, and write down the reading before and after.

The trade map.

AreaWhat it coversWhere to go deeper
SafetyElectricity, brazing fire, A2L, carbon monoxide, falls, old housesSafety first
Local rulesWhich agency by address, County permits and fees, design review, Coastal Zone, noise, fire, flood, climate zone, utilities and rebates for Montecito and Santa BarbaraMontecito and Santa Barbara: your local rules
SystemsSplit AC, heat pump, furnace, mini-split, package unit, ERV/HRV, water heatingHow the systems work; Heat pumps in practice; Mini-splits, multi-zone systems and zoning; Thermostats and smart controls; Ventilation, filtration, humidity and wildfire smoke; Water heaters and hydronic heat; Combustion venting categories and gas leak response
MathLoad, airflow, ducts, refrigerant, moist air, electrical, efficiencyThe math and the 3D math page
ToolsGauges, vacuum, recovery, meters, brazing, duct toolsTools and instruments and the 3D tools page
InstallLine sets, nitrogen test, evacuation, charging, ducts, drains, wiring, A2L sensorsInstallation; Ductwork practice, attics and crawlspaces; A2L refrigerants on the job
Diagnostics25 common failures with test steps, coastal and heat-wave workDiagnostics: the top 25 failures; Coastal air, heat waves and the work day
Code and businessEPA 608, CSLB C-20, Title 24, estimating, contracts, customers, rebatesCode, licensing and permits; Business: contracts, liens and pricing; Customers, upsell ethics, documentation and warranty registration; California rebates and incentives
CourseDay 1 to master stages, first-day tool kit, beginner mistakes, 20 self-check questions, careersDay 1 to master; Careers, certifications and training; Mastery path, glossary and source ledger

How to use the package. Read a section here, then open the matching scene in HVAC Math in 3D and move the sliders until the numbers make sense. The tools and installation sections pair with the HVAC Tools in 3D page, and the math section pairs with HVAC Math in 3D.

How much to trust the numbers. Every fact in this guide was checked against a fetched web page where possible. The source ledger at the end of the guide lists what is confirmed and what is not. Some values differ by manufacturer: nitrogen test pressure and hold time, evacuation decay limit and add-on charge. For those, the guide shows a manufacturer table and sends you to the installation manual. Anything marked UNCONFIRMED is a typical value, not a rule.

Montecito and Santa Barbara: your local rules

Montecito is unincorporated, so the County of Santa Barbara, not the City, issues the mechanical permit, reviews how outdoor equipment looks and sets most of the local rules below. As of 2026-10-28. Anything marked Unconfirmed must be checked with the agency before you quote. Figures from the City of Santa Barbara are labelled CITY OF SANTA BARBARA ONLY wherever they appear in this guide, and they are not Montecito rules.

Which agency, by address

AddressPermit and plan checkDesign review and fireElectricity and gas
Montecito, Summerland (unincorporated)County Planning and Development, Building and Safety Division. Apply on the Citizen Access Portal. Confirmed (County Building and Safety page, County energy page)County Board of Architectural Review under the Montecito Land Use and Development Code. Fire: Montecito Fire Protection District, which has its own standards. Confirmed (BAR packet, County Code Article XIX)Supply: 3CE by default. Delivery: SCE. Gas: SoCalGas, and some homes use propane. Confirmed by region, not by address (County energy page)
City of Santa BarbaraCity Community Development. CITY OF SANTA BARBARA ONLY: the City fee, noise and setback figures in this guideCity review boards and City Fire. Not researched here, so UnconfirmedSupply: Santa Barbara Clean Energy. Delivery: SCE
Carpinteria, GoletaEach city's own building department. Rules not researched here: use their own sourcesNot researched hereNot researched here

A ZIP code or mailing city does not decide the agency. No page read maps a ZIP code to Montecito, so confirm the jurisdiction, the fire district and the Coastal Zone by parcel. The Montecito Fire district map and Summerland's own zoning rules were not read.

Pre-job local checklist

Decision flow: which agency, which permit path

Montecito jobs follow County rules; City figures stay in the CityStart from the parcel, not the ZIP codeMontecito, SummerlandCounty Planning and Development,Building and Safety DivisionCity of Santa BarbaraCity Community DevelopmentCITY ONLY FIGURES:$627 furnace permit53 dBA condenser limit5 ft side, 10 ft frontattic access 30 x 22 x 30 inCarpinteria, GoletaTheir own departmentsRules not researchedCounty pathWhole unit replaced?yesGet a County mechanical permitOnly a component swap is exempt (Code s10-1.6.1)Apply on the Citizen Access Portal before worknoCondenser moved, roof unit added,or line set visible?yesGet a written Director determinationHVAC is not on the design review exemption listDo this before you order or move equipmentnoParcel in the Coastal Zone, or unsure?yesAsk County Planning before you bidParcel boundary unconfirmed; no HVAC exemption foundArticle II exempts repair that does not enlargenoInstalling a heat pump?yesPlan charge verificationRequired for heat pumps in every climate zoneAC in zone 5 or 6 skips it; confirm zone by parcelnoBuild and pass inspectionKeep proof of permit for rebatesA yes answer stacks: finish that step before work.A City address leaves the chart at the second row.
Which agency, which permit path

Read down the County column. Each yes sends you to a step you finish before the work, and the answers stack. The City box holds the figures that must not be reused in Montecito.

Permits and fees (Montecito, County of Santa Barbara)

The County permit is the first step in Montecito. The County fee schedule has no line named for an air conditioner, heat pump or change-out, so quote the closest lines and confirm with the County.

ItemWhat applies in MontecitoSourceStatus
Who issues and where to applyCounty Planning and Development, Building and Safety Division, on the Citizen Access Portal (launched 2023-07-05). The application needs the address, parcel number, ownership information and contacts.County Building and Safety, portal guide v2026.04.23Confirmed
Codes adopted2025 California Mechanical Code and 2025 Energy Code (Ordinance 5270, adopted 2025-11-18). Local Energy Code amendments are not shown on the page read, and the CEC list shows no approved local energy ordinance for the County, the City, Goleta or Carpinteria.County Code Article V, Article VIConfirmed (secondary)
Permit for a whole-unit replacementRequired. County Code Chapter 10, section 10-1.6.1 d.3 exempts only swaps of component parts, and no like-for-like wording was found. Confirm at the Building and Safety counter.County Code Article IConfirmed (secondary)
County fee lines (closest)The schedule effective 2026-07-01 (Fee Ordinance 5271) has no air conditioner, heat pump or change-out line. Closest lines, as the reading tool labelled them plan check and inspection: heating appliance, cooling unit or refrigeration unit add-on 235 and 156; FAU or furnace 235 and 118; air-handling unit with ducts 313 and 156. Confirm with the County which line applies.County fee scheduleClosest lines, confirm
Fees on topHourly plan check $313, issuance fee $156, re-inspection $313 per hour, plus 6.00% technology and 3.70% general plan surcharges. Work started without a permit is charged an investigation fee equal to the fee avoided.County fee scheduleConfirmed
Energy review fee (CF1R, HERS)No energy, CF1R or HERS line on the schedule as read, and no County statement on forms for a mechanical change-out. State Title 24 rules still apply (see the Code section).County plan submittal pageUnconfirmed
Application checklist and over-the-counter pathThe County says submittal requirements vary by project, and no HVAC checklist was found. Whether furnace, AC or heat pump change-outs are issued over the counter is unknown; a 2023 article cites water heater replacements as an example.County plan submittal page, Edhat, 2023-07-05Unconfirmed
Permit lifeThe application expires 365 days after filing, with one extension of up to 180 days. The permit is invalid if work has not started within 12 months or is suspended for 180 days.County Code Article IConfirmed (secondary)
Other agency approvalThe Building Official may require approval from water and sewer districts before issuing a permit.County Code Article IConfirmed (secondary)
CITY OF SANTA BARBARA ONLY: feesCity FY26 schedule (effective 2025-09-01): $627 for a furnace new or replacement and $315 for a wall heater, with no A/C or heat pump line. Like-for-like jobs at single-unit homes and duplexes can use the City's On-Demand portal. Do not quote these for a Montecito job.City fee scheduleCity only

The County Code pages are read from the gocodebook.com republisher, not the County's own site, so they are secondary text.

Design review for outdoor equipment (Montecito)

HVAC is not on any exemption list that was read, so a condenser move, a rooftop unit or a visible line set may need design review. Get the answer in writing from County Planning before you order equipment.

TopicWhat the sources sayStatus
Required findingThe Board of Architectural Review may approve only if mechanical equipment is "well integrated" in the total design.Confirmed (MLUDC section 35.472)
GuidelinesMontecito Architectural Guidelines (May 2016): outside mechanical equipment, including air conditioning, "should be architecturally integrated into building or site design" (III.G.3.b, p. 21), and condensers "should be located or buffered" (III.C.3.h, p. 17). The guidelines say should; the finding is mandatory once review applies. They say nothing on heat pumps, roof units, line sets or ground-mounted equipment.Confirmed (Guidelines, hosted by the Montecito Association; County adoption not checked)
ExemptionsDesign review exceptions do not name HVAC. Exempt: accessory dwelling units, interior alterations, solar panels, decks, fences and walls of 6 ft or less, spas and pools, and "other exterior alterations determined to be minor by the Director". The County BAR packet (2026-07-31) lists no HVAC either.Confirmed (BAR packet)
Route for a condenser move, roof unit or visible line setAsk County Planning for a written Director determination that the work is minor, before you move or add equipment. If review applies, the BAR meets every other Thursday at 123 E. Anapamu St., applications are due 2 pm Thursday three weeks before, and appeals go to the Montecito Planning Commission.Practice-based route; no rule names condensers, roof units or line sets (BAR packet)
Planning exemptionsRepair and maintenance without enlargement, and in-kind replacement of a conforming structure that is not larger and is under 50 years old, are exempt from planning permits. No HVAC line. This is separate from the building permit.Confirmed (MLUDC section 35.420). Whether a condenser counts as a structure: Unconfirmed
SetbacksMontecito R-1 and E-1 zones: front 20 ft, side 10% of lot width with a 5 ft minimum and 10 ft maximum on lots under 2 acres, rear 25 ft. DR zone: side 10 ft. Setbacks must be clear from ground to sky except listed projections, and condensers are not listed. Whether a ground condenser may sit in a side setback is Unconfirmed: ask Planning first.Confirmed for the zone figures (MLUDC residential zones). Zone by parcel. Do not use the City's 5 ft and 10 ft
Historic or special districtsNo Montecito rule on HVAC found. The County Historical Landmarks Advisory Commission was not read.Unconfirmed

Coastal Zone

Do not promise that a like-for-like swap is exempt. The Montecito parcel boundary is not confirmed, and no HVAC exemption wording was found.

TopicWhat the sources sayStatus
Which Montecito parcels are in the Coastal ZoneNo page read gives a parcel or street boundary. Montecito was under the Article II Coastal Zoning Ordinance until the stand-alone Montecito code. Check the parcel on the County coastal map or ask Planning.Unconfirmed (Coastal Commission report, 2010)
Repair and maintenance exemptionArticle II section 35-51B.B.7.a exempts repair and maintenance from a Coastal Development Permit if it does not enlarge the object and complies with Appendix C. B.7.b removes the exemption for extraordinary methods with adverse environmental risk. No HVAC or like-for-like wording was found. Appendix C and section 35-169 were not read.Confirmed for the text read (Article II). HVAC application: Unconfirmed
Where the exemption stopsIt is not available next to a wetland, stream, beach or environmentally sensitive habitat, and it needs the setbacks and any other required permit to be met.Confirmed (Article II)
State rule behind itThe Coastal Act exempts repair or maintenance that does not add to or enlarge the object, except extraordinary methods.Confirmed from republished text (Public Resources Code 30610)
CITY OF SANTA BARBARA ONLYThe City handout has no equipment-replacement category, and anything not excluded or exempt needs a Coastal Development Permit. Do not apply the City coastal map to a County parcel.Unconfirmed (City handout)

Noise

No Montecito equipment noise limit was found. The County nighttime noise chapter is about amplified sound, so how it applies to a condenser is uncertain. Place and buffer the unit as if a limit applied.

TopicWhat the sources sayStatus
County nighttime noise (Chapter 40, not Chapter 36)Quiet hours are 10 pm to 7 am Sunday to Thursday and midnight to 7 am Friday and Saturday. "Loud and unreasonable" means clearly discernible 100 ft from the property line, or over 60 dB at the property line, and enforcement does not need a meter. Fines are $100, $200 and $500. The listed sources are amplified devices such as radios and loudspeakers, with no HVAC wording and no dB(A) weighting.Confirmed text (County Code Chapter 40). Application to a condenser: Unconfirmed
County daytime equipment limitNone found. The Noise Element thresholds were not read.Unconfirmed (County noise page)
Design guidelineCondensers "should be located or buffered" to reduce noise on neighbors (Montecito Architectural Guidelines III.C.3.h).Confirmed (Guidelines)
Construction hoursNo County rule found. Permit conditions may set hours, so ask Planning.Unconfirmed
CITY OF SANTA BARBARA ONLYCondensers: 53 dBA at the property line of an adjacent residential parcel (SBMC 9.16.070.D). Construction is restricted from 8 pm to 7 am, and after-hours work needs a special permit from the Chief Building Official at least one week ahead.Confirmed (City Noise Guide, after-hours sheet 2024-04-17)

Fire and wildfire zones (Montecito Fire Protection District)

Montecito Fire has its own Development Standards, separate from County Fire. Do not use County Fire's Standard 6 or the City's vent sheet on a Montecito job.

TopicWhat the sources sayStatus
Adopted code and zonesThe standards (November 2025, updated 2026-02-02) cite the 2025 California Wildland-Urban Interface Code and Ordinance 2025-02. Defensible space is 100 ft: Zone 0 is 0 to 5 ft, Zone 1 is 5 to 30 ft, Zone 2 is 30 to 100 ft.Confirmed (Montecito Fire standards); text of Ordinance 2025-02 not read
Zone 0Item c: "No items that are likely to be ignited by embers". Items b, d and e apply to existing structures. Equipment is not named. A condenser is not ignitable on its face; a wood pad, plastic cover, combustible screen or mulch around it is.Confirmed text; the equipment reading is Practice-based
Fuel-fired furnace sprinklersOn sprinklered projects, one intermediate-temperature head over each fuel-fired furnace, 18 in from diffuser grilles and 2 ft from heat or return registers. Applies to new and major projects.Confirmed (Montecito Fire standards)
Alterations to an existing buildingCounty Code Article XIX applies the WUI Code to the altered area only, with an exception when under 50% of the roof framing or wall finish is replaced. So a swap that does not touch the roof or wall finish should not trigger the vent upgrades. That is an inference, and the Montecito ordinance text was not read.Inference (County Code Article XIX)
Vent meshMontecito's vent mesh rule was not found. County Fire Standard 6 (1/16 in noncombustible mesh, 144 sq in maximum opening) applies to County Fire's area, and the City's 2019 sheet asks for 1/8 in mesh. The agencies differ, so do not carry a number across.Unconfirmed for Montecito (County Fire Standard 6, City sheet, 2019)
Condenser, gas meter and gas line clearance, duct openingsNot addressed in the standards read. Propane tanks need 10 ft to bare mineral soil in Zones 1 and 2.Unconfirmed

Flood, debris flow and water

TopicWhat the sources sayStatus
Equipment in the floodplainEquipment in new construction, substantial improvements and other new development must be designed or located to keep water out. No HVAC mounting height is given. Whether a like-for-like change-out is "development" is not stated.Confirmed text (County Code Chapter 15A). Change-out application: Unconfirmed
Elevation figuresThe lowest floor must be 2 ft above base flood elevation. A substantial improvement costs 50% or more of the structure's market value over 10 years.Confirmed (Chapter 15A)
Debris-flow Recovery MapThe FEMA Recovery Map after the January 2018 debris flow is part of the County floodplain rules, and where its advisory elevation is higher, the higher one governs.Confirmed (Chapter 15A)
Where to put the outdoor unitRaise a replaced condenser on a pad above the expected water level if the site has flooded.Practice-based
Flood Control reviewCounty Public Works Flood Control reviews Building and Safety permits. The page was not read. City floodplain rules were not researched.Unconfirmed (County page)
CondensateThe County storm drain code lists air conditioning condensation as an exempt discharge if properly managed and not found to cause pollution or nuisance. Montecito Sanitary District rules and the City's Title 16 do not name condensate.Confirmed for the County storm drain (County Code Chapter 29); sewer: Unconfirmed
AnchoringThe 2025 California Mechanical Code requires fixed appliances to be fastened per the manufacturer's instructions, with supports sized for vertical and horizontal loads. A County or City amendment for wall or roof equipment was not found.Confirmed (CMC 303.4); local amendment: Unconfirmed

Climate zone and Title 24 consequences

Montecito's coast and valley are in climate zone 6 and the upper foothills are in zone 5, and both are outside the zones where an air conditioner needs charge verification. A heat pump needs it in every zone. Confirm the zone by parcel.

TopicWhat the sources sayStatus
Zone by placeThe CEC Building Climate Zones layer returns zone 6 for Montecito's coast and valley, the City of Santa Barbara, Carpinteria, Summerland and Goleta. Points above about 34.455 N in upper Montecito return zone 5.Confirmed from point queries (CEC layer on ArcGIS); the host is not energy.ca.gov, so the CEC ownership is inferred from the layer description
What was not readThe CEC ZIP table (BuildingClimateZonesByZIPCode_ada.xlsx) came back as binary and the CEC lookup app would not render. A jurisdiction may assign one zone to a whole ZIP. Confirm the zone for each address with the CEC lookup and the CEC zone page.Unconfirmed
Conflicting tableA 2016 CAPCOA table lists ZIP 93108 and 93101 as zone 8. It is a secondary compilation and conflicts with the CEC layer, so it was set aside. If zone 8 were right, an air conditioner would need charge verification.Conflict, resolved in favour of the CEC layer (CAPCOA, 2016)
Charge verificationAir conditioners only in zones 2 and 8 to 15, and heat pumps in all zones. So a Montecito heat pump needs it, and an air conditioner in zone 5 or 6 does not.Confirmed (CEC)
County energy formsThe County adopts the 2025 Energy Code as amended, and the amendments are not shown. How the County handles CF1R and HERS for a mechanical change-out was not found.Unconfirmed

Gas furnaces and the air district

TopicWhat the sources sayStatus
County gas ruleNo adopted County ordinance bans gas in new buildings or replacement appliances. In September 2024 the Board voted 3 to 2 to direct staff to draft an energy reach ordinance that encourages all-electric new buildings, with no retrofit mandate. Its later status is unknown.Unconfirmed (Santa Maria Times, 2024-09-18)
CITY OF SANTA BARBARA ONLY: gasThe City's 2021 ordinance covers newly constructed buildings only, for permit applications after 2022-01-01, and does not address replacing a furnace in an existing home. An all-electric replacement rule was only a proposal (BE-5.1), and its 2026 status is unknown.Confirmed for the new-building scope (City press release)
Air district Rule 352Anyone who makes, sells or installs a natural gas fan-type central furnace in the Santa Barbara County district must meet a NOx limit of 40 ng/J (55 ppm at 3% O2), with certification. SCAQMD certificates are accepted. So confirm the model is certified before you quote a gas furnace. That last step is an inference.Confirmed for the 2011 text (Rule 352); later amendments unknown

Utilities and incentives for Montecito

TopicWhat the sources sayStatus
Electric and gas utilities3CE is the default electric supplier for unincorporated areas, SCE delivers, and SoCalGas supplies most gas. The County page does not name Montecito, so confirm the customer's account is with 3CE and not opted out to SCE.Confirmed by region (County energy page)
3CE Electrify Your Home, heat pump HVACInstalls from 2026-08-01 to 2027-09-30, with the application due by 2027-09-30, first come first served. It replaces a non-electric appliance, must be electric-only with no gas backup, and a split needs ENERGY STAR or SEER2 above 15.2 and HSPF2 above 7.8. One rebate per outdoor unit and two HVAC rebates per account per fiscal year. Proof of permit is required.Confirmed (3CE)
3CE dollar amountsThe 2026-10-01 amounts are in an image that could not be read. The 2025 flyer showed $2,000, or $3,000 income-qualified, and may be superseded. Call 3CE at 1-877-455-2223.Conflict (2025 flyer)
Stacking and income tier3CE rebates can be combined with other rebates up to 100% of project cost. Income-qualified means CARE or FERA, or the table threshold.Confirmed (3CE)
TECH and HEEHRATECH single-family heat pump HVAC is closed to new reservations (notice 2025-11-14), and HEEHRA single-family rebates were fully reserved statewide on 2026-02-24. An SCE fact sheet still lists $1,000 per heat pump, so treat it as closed.Conflict (TECH, SCE fact sheet)
CITY OF SANTA BARBARA ONLY: SBCEThe Santa Barbara Clean Energy program (applications 2026-07-01 to 2027-06-30) is for SBCE customers in the City, and Montecito is not mentioned. The $820 permit fee help is also a City figure.Confirmed (SBCE guidelines)
SoCalGas rebates, SCE panel and service upgradesNo current SoCalGas HVAC rebate page and no SCE panel or service guidance for heat pumps were read. The County has a residential panel upgrade guide on the same portal.Unconfirmed

Quote any rebate as "may qualify" and point to the live page, because the proof of permit is the County permit and funds run out.

Open items: confirm before you quote

None of these was confirmed. Tick each one when you have the answer from the agency.

Safety first

Five hazards injure HVAC technicians: electricity, fire from brazing, flammable refrigerant, carbon monoxide, and falls. Learn these before touching a tool.

HazardWhat injures youThe ruleStatus
ElectricityShock, arc flash, and charge stored in a run capacitor after power is offTurn the disconnect off, lock it, tag it, and prove the circuit dead with a meter you tested on a known live source. Discharge a capacitor through a resistor, never a screwdriver.Title 8 section 3314 covers lockout and tagging for servicing machines but excludes energized electrical work (source): confirmed. The resistor size commonly taught (about 20k ohm, 2 W) is a field rule of thumb: unconfirmed.
Fire from brazingBurns and a structure fire started inside a wall or atticClear combustibles, protect framing with a heat shield, keep an extinguisher in reach, watch the area after you finish. Flow nitrogen through the line while you braze so the inside does not scale.Cal/OSHA Article 88 requires fire prevention procedures, based on ANSI Z49.1 and NFPA 51B (source): confirmed. Fire-watch length (30 to 60 minutes is commonly taught) and a 10 ft clearance: unconfirmed, so follow your employer's hot-work permit.
Mildly flammable refrigerant (A2L)Ignition of a leak; slow burning is still burningUse A2L-rated recovery machines, manifolds and leak detectors. Remove ignition sources, ventilate, and never use a standard recovery machine on an A2L system.R-32 and R-454B are class 2L with a burning velocity under 10 cm/s (AHRI): confirmed. R-454B flammability limit: Chemours lists 11.5 vol% nominal and 0.354 kg/m3 at worst-case fractionation, but ACHR lists 11.8 vol% and a sensor vendor 0.303 kg/m3, so sources conflict and the equipment manual rules (Chemours). California building code adopts CMC 2025 (LADBS): confirmed. R-32 limit and cylinder markings: unconfirmed, read the equipment installation manual.
Carbon monoxidePoisoning from a cracked heat exchanger, blocked vent or backdrafting applianceTest every furnace and water heater after any service. Flue limit is 400 ppm CO air-free (ANSI Z21.47).OSHA permissible limit 50 ppm over 8 hours, NIOSH recommended limit 35 ppm, 1,200 ppm immediately dangerous to life (OSHA): confirmed. The 400 ppm air-free flue limit (ServiceMag): confirmed. Residential CO alarm duty (Health and Safety Code 17926, from SB 183): confirmed.
FallsFalls from roofs, attics and laddersFall protection starts at 6 ft. A personal fall arrest system limits arrest force to 1,800 lb, free fall to 6 ft and deceleration distance to 3.5 ft. A ladder extends 3 ft above the landing, sits at a base distance of one quarter of its working length, and you never stand on the top step.Fall protection at 6 ft (OSHA 1926.501) and the arrest limits (1926.502): confirmed. Ladder numbers: confirmed in the source ledger.
Old housesLead dust and asbestos fibers from disturbed paint, duct wrap, flue pipe or tileIn pre-1978 homes, paid work that disturbs paint needs an EPA lead-safe certified firm unless it falls under the minor repair limits (6 sq ft inside, 20 sq ft outside). In California, asbestos-related work of 100 sq ft or more needs an asbestos certification. If you cannot tell what a material is, stop and have it tested.EPA lead rule and the 6 and 20 sq ft limits, and the 100 sq ft certification (CSLB asbestos certification): confirmed. Cal/OSHA section 1532.1 sets the lead limit at 10 ug/m3 with an action level of 2 ug/m3, and the silica limit is 50 ug/m3: confirmed. The 1980 "asbestos cutoff" is a rule of thumb, unconfirmed: some products used asbestos later.

In the 3D tools page, every scene opens with its safety notes first.

Scenes to open: In HVAC Tools in 3D, open Protect your eyes, hands, lungs and ears, Ladder angle and fall arrest on a roof, Braze a copper joint safely and Lock out, then prove it is dead: tester, meter and 24 V.

How the systems work

Every system moves heat with a fluid. A refrigerant loop moves heat through a coil. Air carries it through ducts. A furnace makes heat by burning gas, and a heat pump moves heat instead of making it. Learn the loop once and every system becomes a variation.

The refrigerant loop. Four parts, in order:

  1. The compressor raises the refrigerant's pressure and temperature.
  2. The condenser rejects heat to the outdoor air and turns the gas into liquid.
  3. The metering device drops the pressure, which chills the liquid.
  4. The evaporator absorbs heat from the indoor air and boils the liquid back into gas.

The gauge readings you take, superheat and subcooling, tell you how full the evaporator and condenser are. The 3D math page animates this loop.

One loop carries heat from indoor air to outdoor air by changing pressureINDOORSOUTDOORSEvaporatorboils liquid to gas118.4 psig = 40 FCompressorraises pressureand temperatureCondenserturns gas to liquid317.6 psig = 100 FMetering devicedrops the pressureLow-pressure gas(superheated vapor)High-pressurehot gasHigh-pressure liquid(subcooled)Cold, low-pressureliquid-vapor mixHeat inHeat out tooutdoor airLow-pressure sideHigh-pressure sidePressures are R-410A saturation values computed with CoolProp.
The refrigerant loop

Read the loop clockwise from the compressor. Pressure and heat go up there. Heat leaves at the condenser, and pressure drops at the metering device. The evaporator then boils the liquid by absorbing house heat.

SystemHow it worksWhere it fitsWatch for
Split air conditionerOutdoor condenser plus indoor coil on a furnace or air handlerHomes with ducts that only need coolingMatched coil and condenser; airflow across the coil
Heat pumpThe same loop with a reversing valve, so it heats or coolsMild climates like coastal CaliforniaDefrost cycle, backup heat, and the O or B wire on the thermostat
Gas furnaceBurns gas, passes the hot gas through a heat exchanger, blows house air across itCold winters, low gas costFlame sensor, pressure switch, flue venting and CO
Ductless mini-splitOne outdoor unit feeds one or more wall or ceiling heads, no ductsAdditions, older homes without ductsLine set length and charge adjustment, condensate drain
Package unitEverything in one cabinet outdoors, connected to the house by ductsRoof or slab installs with no indoor spaceWeather sealing, duct connections
ERV and HRVSwap stale indoor air for fresh outdoor air and recover part of the heatTight, well-insulated housesFilters, balanced airflow, condensate in cold weather
A gas furnace lights only if each step proves itself before the nextTHE SEQUENCEIF IT STOPS HERE1Thermostat closes R to W: a heat call2Board checks limit and rollout switches3Inducer starts, pressure switch closes4Igniter warms up and glows5Gas valve opens at 24 V and burners light6Flame sensor proves flame (microamps)7Blower starts after a delay8Call ends: gas stops, fans run on, then stopLimit or rollout open: no start,read the board LED codeSwitch will not close: blocked vent,tube or trap, bad inducer or switchIgniter stays dark: failed igniteror no 120 V at its plugBurners do not light: 24 V at thevalve during the trial, then gas supplyFlame drops out: dirty flame sensor,then the board retries and locks outDelays, trial time and retry count vary by brand: typical value, check the manufacturer manual.
Gas furnace ignition sequence

Watch a call for heat run down the left column, and when it stops, the step where it stopped points to the right-hand cause to test first.

Which refrigerant. R-410A has been the standard for residential systems. New equipment is moving to the mildly flammable A2L refrigerants R-32 and R-454B. California's limit on global warming potential for new ducted systems is under 750 (see the code section). A2L equipment needs A2L-rated tools and different handling.

Why matching matters. Compressor, coil, metering device and furnace are designed as a set. A mismatched coil changes pressures, airflow and capacity, and the manufacturer's rating no longer applies.

A split system is two units joined by two copper lines and a thermostat wireThermostatsends 24 V callsOutdoor unitCompressorCondenser coil and fanRun capacitor and contactorService valvesFurnace or air handlerEvaporator coilMetering deviceBlower and filterDrain pan and drain lineSuction line: larger, insulatedLiquid line: smallerDisconnect and breakersized to MCA and MOPline voltageRooms of the housereached through ductsReturn airSupply airRefrigerant vaporRefrigerant liquid24 V control wire
Split-system component map

The suction line carries cool vapor back to the compressor. The liquid line carries warm liquid out to the metering device. The thermostat only sends 24 V calls, and the disconnect feeds the outdoor unit's line voltage.

For a heat pump in the mild coastal climate of Montecito and Santa Barbara (zone 6 on the CEC layer, so charge verification applies; confirm the zone by parcel), the defrost and backup heat questions matter less than in a cold climate. The heating-versus-cooling load balance still decides the size, so size from the load calculation, never from the old unit.

What a master checks first, by system

The order is always airflow, then electrical, then refrigerant or combustion last. Only the first and second checks change from system to system.

SystemCheck firstThenNever skip
Split air conditionerAirflow: filter, coil face, blower wheel, registers and static pressure24 VAC at the control, line voltage, capacitor uF, amps against the nameplateSuperheat or subcooling after 10 to 15 minutes, against the manufacturer chart
Heat pumpThermostat O/B setup and 24 VAC at the reversing valve solenoidAirflow, then the defrost sensor and boardTreat a tap on the reversing valve as a diagnostic, not a repair
Gas furnaceThe board LED code, then watch the sequence: inducer, pressure switch, igniter, gas valve, flameAirflow and temperature rise against the nameplate, flame sensor microampsA CO test after any service, and never jump out a safety
Ductless mini-splitFilter, indoor coil and condensate drainLine set length and the charge adjustment for it, flare torque from the manualWeigh in the charge by the manufacturer's rule
Package unitFilter, coil and blowerWeather sealing and duct connectionsSuperheat or subcooling after the system is stable
ERV and HRVFilters and balanced airflowCondensate in cold weatherCheck both airstreams, not one

Scenes to open: In HVAC Math in 3D, open Airflow per ton and the temperature split, Superheat: how far past boiling, Subcooling: how far past condensed and Furnace input, output and temperature rise. In HVAC Tools in 3D, open Read the gauges: pressure to saturation temperature, Static pressure: supply plus return is the TESP and Delta T: supply and return temperature.

Heat pumps in practice: defrost, backup heat and balance point

Heat pumps lose capacity as outdoor air gets colder, so defrost, backup heat and thermostat setup decide how winter feels.

Choosing the system. Two facts pick the system: whether the house has usable ducts, and how cold winters get. The Department of Energy (DOE) says cold-climate heat pumps are designed for outdoor temperatures as low as 5 F, and that in a dual-fuel setup a furnace takes over in colder weather (DOE). Status: confirmed.

Ducts and winter cold pick the systemUsable ductsin the house?Long freezingwinters?Ductless mini-splitNeeds only a 3 in. wallhole (DOE)Ducted heat pumpMild coast, such as Santa BarbaraCharge check required (CEC)Cold-climate heat pump,or dual fuel with a furnaceENERGY STAR cold climate label;built for as low as 5 F (DOE)yesyesnonoReusing ducts? Check their size and the return capacity first.
System choice flow

Start at the ducts: no usable ducts points to a mini-split, and with ducts the winter decides between a standard heat pump and a cold-climate or dual-fuel setup.

TopicWhat to doStatus
DefrostIn heating, the outdoor coil can frost over. The reversing valve flips the refrigerant flow to melt the frost. Choose a unit with demand-defrost control, which defrosts only when needed.Confirmed (DOE)
Defrost testForce a defrost cycle as the manual describes, check the defrost sensor against its chart, and clear ice and drains.Practice-based. Sensor values in the diagnostics table are typical values, check the manufacturer manual
Backup heatElectric strip heat or a gas furnace covers what the compressor cannot. Emergency heat runs the backup alone and leaves the compressor off.Practice-based
California backup lockoutA thermostat on a heat pump with supplementary heat must get the outdoor temperature, display it, and show when backup heat runs. It must lock out supplementary heat above 35 F, except during defrost or when the user picks emergency heat.Confirmed from a code-publisher excerpt (gocodebook). Section labels on that page conflict, so check the adopted code
Balance pointThe outdoor temperature where heat output equals the house's heat loss. Below it, backup heat runs. Find it by comparing the manufacturer's capacity data with the Manual J heating load.Practice-based. The value is specific to each job
AirflowDOE aims for roughly 400 to 500 CFM per ton and warns that performance drops when airflow falls well below 350. California verifies at least 350 for new systems.Confirmed (DOE, CEC). The sources differ, so use the manufacturer's blower table
Duct sizeA heat pump delivers air at about 80 to 115 F, where a furnace delivers 130 to 140 F. The same ducts may need to move more air, so check duct size and return capacity.Confirmed (Building America guide, 2011)
SizingIn a cold climate a heat pump may be sized above the Manual S result to cut backup heat use. In a mild climate such as coastal Montecito and Santa Barbara, size to the load.Cold-climate note confirmed (same guide). Mild-climate advice is practice-based
ChargeCalifornia requires refrigerant charge verification for heat pumps in every climate zone.Confirmed (CEC)
Outdoor unitKeep it away from windows and neighboring buildings, and shield it from strong wind, which can cause defrost problems.Confirmed (DOE)

The DOE pages show no publication date and were fetched on 2026-10-28.

Mini-splits, multi-zone systems and zoning

A mini-split needs no ducts, so the install work is the line set, the wall hole, the drain and the commissioning checks.

The Department of Energy (DOE) says a ductless install needs only a three-inch hole through the wall (DOE). It also reports that about 32% of homes in colder zones lack ductwork (DOE). The table below comes from one real manual, the Daikin R-32 split installation manual (footers dated 2026-06-12). Other brands differ, so read the manual for the unit you install.

CheckWhat the Daikin R-32 manual saysStatus
Line lengthMinimum 10 ft. Maximum 65-5/8 ft (20 m) on the 09 and 12 size models, and 98-1/2 ft (30 m) on the larger models.Confirmed (Daikin manual, p. 6)
Extra chargeAdd 0.22 oz/ft (20 g/m) for pipe beyond 49-1/4 ft (15 m). Other brands differ: a Mitsubishi R-410A manual gives about 0.216 oz/ft beyond 25 ft, and one R-454B brand gives 0.11 oz/ft beyond 25 ft.Confirmed (Daikin, Mitsubishi FS06, Pioneer)
InsulationInsulate both the gas and liquid lines. Minimum thickness is 13/32 in (10 mm) for the sizes listed.Confirmed (Daikin manual, p. 9)
Outdoor unitInstall on a horizontal surface, tilted 3 degrees or less, with the outlet-side wall 47-1/4 in or lower. Use four anchor bolts.Confirmed (Daikin manual, p. 7)
FlaresUse a clutch-type flare tool. Tighten 3 to 4 turns by hand before the torque wrench. Do not put refrigeration oil on the flare or threads. Torque for 3/8 in is 24.1 to 29.4 ft-lb.Confirmed (Daikin manual, pp. 8 to 9). The tools section allows a drop of oil on some units, so follow the manual for yours
Pressure test604 psi, held at least 1 hour, with 24 hours recommended. Check flares and valve stems with soapy water, never a flame.Confirmed (Daikin manual, p. 10)
VacuumBelow 500 microns for at least 1 hour. Close the valve, stop the pump, and confirm the gauge does not swing back.Confirmed (Daikin manual, p. 10)
Stop valvesOpen with a 3/16 in hex wrench. Do not operate them when the outdoor temperature is -5 F or lower.Confirmed (Daikin manual, p. 10)
DrainHeat pump models only. In cold areas do not use the drain socket, because water may freeze. Use a 5/8 in inner diameter hose. Wait at least 5 minutes after stopping before turning off power.Confirmed (Daikin manual, pp. 3 and 8)
A2LThe unit holds R-32, a class A2L refrigerant that is heavier than air. The minimum room floor area depends on charge and mounting height, and is listed in the indoor unit's safety document. This manual says nothing about a sensor.Confirmed (Daikin manual, pp. 2 to 6). Read the indoor unit documents too
CommissioningAfter the breaker goes on, the unit may blow no air for about 15 minutes. Check secure mounting, no leaks, insulated lines and drain, ground, wiring, clear air paths, open stop valves, and a response to the remote.Confirmed (Daikin manual, p. 18)

Multi-zone systems. One outdoor unit can feed several indoor heads. The manufacturer limits the total connected capacity and the line length to each head, so use that brand's multi-zone table rather than one head's manual. Status: practice-based, typical value, check the manufacturer manual or code.

Zoning a ducted system. Zoning uses motorized dampers to send air only to the rooms that call. It is easy to do badly:

Thermostats and smart controls

A thermostat is a set of switches that send 24 V calls, so most smart-thermostat problems are wiring and setup, not software.

The terminal jobs (R, C, W, Y, G, O/B) are in the Installation section's wiring diagram. This table covers what changes when the thermostat is smart, programmable or on a heat pump.

TopicWhat to doStatus
Power and the C wireA smart thermostat needs the 24 VAC common. With no C wire, use a spare conductor in the cable, or fit a C-wire adapter or a transformer. Test 24 to 28 VAC from R to C before you leave.Practice-based. The 24 to 28 VAC range is in the install steps
Heat pump setupSet O or B for the brand, the number of stages, and the backup heat lockout. California requires the lockout above 35 F, an outdoor temperature display and a backup-heat indicator. The installer certifies the test on the Certificate of Installation.Confirmed from a code-publisher excerpt (gocodebook). Section labels on that page conflict, so check the adopted code
Setback scheduleA system not run by an energy management control system needs a setback thermostat whose clock lets the occupant program setpoints for at least four periods in 24 hours. Room heaters, fireplaces and room air conditioners are exempt.Confirmed (same page, section 110.2(c))
Demand responseA demand-responsive thermostat must be certified to the Energy Commission, respond to a utility signal (OpenADR 2.0b or 3.0), and meet Joint Appendix 5. A Wi-Fi connection alone does not make a thermostat compliant.Confirmed (same page, section 110.12(a))
Variable-speed equipmentA third-party thermostat on a variable or multi-speed system must still let the compressor modulate to meet the load. Many makers use their own thermostat for this reason.Rule confirmed (same page, section 150.0(h)9). The advice about makers is practice-based
Setback on a heat pumpA deep morning recovery can start the backup heat, which costs more than the setback saves. Limit the setback or use the thermostat's recovery setting.Practice-based, typical value, check the manufacturer manual
HandoffShow the customer the backup-heat indicator, the schedule and the Wi-Fi sign-in. Write down every setting you changed.Practice-based

Ventilation, filtration, humidity and wildfire smoke

Clean, moderately humid air takes filters, fresh-air ventilation and humidity control together, and each one has limits you should explain to the customer.

TopicWhat to doStatus
Filter gradeEPA recommends a filter rated MERV 13 or higher, or the highest rating the system can take. MERV is a rating of how well a filter catches small particles, and a higher number catches finer ones. Confirm the blower can handle it by reading static pressure after the swap.Confirmed (EPA, updated 2026-10-01). The static pressure check is practice-based
Filter limitsA filter cleans air only while the blower runs, and systems usually run less than 25% of the time. Manufacturers typically say to replace filters every 60 to 90 days.Confirmed (same EPA page)
OzoneAvoid air cleaners and filters that make ozone on purpose, such as ionizers, electrostatic precipitators, and UV lights without adequate lamp coatings.Confirmed (same EPA page)
Humidity rangeKeep indoor relative humidity between 30 and 50 percent, and below 60 percent. Dry anything wet within 24 to 48 hours. Do not run the HVAC system if you know or suspect mold in it.Confirmed (EPA, updated 2026-02-18)
Oversizing and damp airOversized equipment cycles too often, and poor airflow leaves the air overly damp. Both are found by the load calculation and airflow checks in this guide.Confirmed (ENERGY STAR, undated page)
ERV and HRVBoth bring in a constant flow of fresh air while exhausting stale air, and the outgoing air pre-warms or pre-cools the incoming air. An ERV also exchanges moisture.Confirmed (AHRI, undated page)
ERV or HRV for Montecito and Santa BarbaraWhich one suits a mild coastal climate depends on indoor humidity and the model.Unconfirmed: typical value, check the manufacturer manual or code
ERV placement and carePut the fresh-air intake away from driveways, laundry rooms and furnace vents. Keep exhaust outlets at least 10 ft from a cooktop or oven. Clean filters every 1 to 3 months, and clean the core and condensate drain every 6 months.Confirmed (AHRI page)

ERV sizing example. AHRI sizes an ERV for at least 0.35 air changes per hour: volume divided by 60, times 0.35. A 2,000 ft2 house with 8 ft ceilings holds 16,000 ft3. That gives 16,000 / 60 x 0.35 = 93.3 CFM. The ASHRAE 62.2 example in the math section gives 90 CFM for the same floor area, so the two methods agree closely.

Wildfire smoke. EPA's guidance, updated in August and September 2026, is short:

Status: confirmed. The DOE and EPA pages were fetched on 2026-10-28.

Water heaters and hydronic heat

Water heaters and hot-water (hydronic) heating belong in an HVAC guide only where they share air, venting, ducts or water with the heating system.

TopicWhat to knowStatus
Heat pump water heaterIt is two to three times more efficient than an electric resistance heater. It needs ambient air of 40 to 90 F all year and at least 1,000 ft3 of air space, and it cools the room it sits in.Confirmed (DOE, undated page)
Its condensateA heat pump water heater pulls moisture from the air, so plan a drain.Practice-based. The DOE page does not cover condensate
Shared closetSwapping a gas water heater for an electric one, or a furnace for a sealed condensing model, changes the combustion air and venting for whichever gas appliance stays. Recheck both.Practice-based, typical value, check the manufacturer manual or code (NFPA 54 or the adopted gas code)
Shared flueA natural-draft water heater that shares a flue with an old furnace may be left with a vent that is too large after the furnace becomes a condensing unit.Practice-based. See the venting categories section
Hydronic heat mathWater carries heat as 500 x GPM x temperature drop. Example: 3 GPM cooled by 20 F delivers 500 x 3 x 20 = 30,000 BTU/h.Constant derived in the math section; arithmetic re-checked in code
Radiant floorsThe circulating water runs cooler than for baseboard, with one example of about 80 F in winter. The floor surface sits only a few degrees above the room, about 75 F at a 70 F setting.Confirmed (GreenBuildingAdvisor, 2021)
Radiant constructionPEX tubing loops run to manifolds fed by a boiler or water heater. They are stapled under the subfloor, embedded in concrete, or set in grooved underlayment. A leak in embedded tubing is hard and costly to repair, and a slab on grade needs insulation under it.Confirmed (same article)
Boiler sizeA 75,000 or 80,000 BTU/h boiler is overkill for a well-insulated, air-sealed house. Size from the load calculation.Confirmed (same article)
Radiant coolingSurfaces below the dew point sweat, so humidity must be controlled. A Building America guide does not recommend radiant floor cooling in humid climates.Confirmed (GreenBuildingAdvisor article; Building America guide, 2011)
LicensingThe CSLB C-20 scope lists water-heating heat pumps. Whether boiler and hydronic piping work needs another classification is not confirmed here.C-20 scope confirmed (CSLB). Hydronic classification: unconfirmed, ask CSLB

Combustion venting categories and gas leak response

A furnace's venting category tells you how its flue gas moves and what pipe can carry it, and a gas leak means leave first and fix later.

CategoryHow it ventsFlue gas and condensationKey install points
ILow to standard efficiency, non-condensing, takes room air. The flue stays at negative pressure.Hot enough that condensation is not expectedNever use the combustion appliance zone as the return air plenum. Check combustion and dilution air. Run a combustion safety test after install.
IIThe source covers only some commercial furnaces and does not describe this category.Not coveredRead the manufacturer's venting instructions
IIIStandard to high efficiency, non-condensing, forced draft. The flue stays at positive pressure while the burner fires.Above 140 F, no condensationMostly oil furnaces. Vent through a wall or roof, direct vent preferred.
IVHigh efficiency, condensing, sealed combustion, with two heat exchangers. The vent is under positive pressure.Under 140 F, condenses on purpose. The condensate is acidic, pH 3 or lower.PVC is acceptable. Use a separate combustion air pipe. Slope the horizontal vent toward the furnace. Drain and neutralize condensate. Add a backup drain pan.

Status for the table: confirmed (Building America resource guide, PNNL, undated page, which cites NFPA 54). Vent and pipe sizing is table-driven. Use NFPA 54, the International Fuel Gas Code or the manufacturer's tables, never a guess.

If you smell gas or find a leak. These steps come from a gas utility's public safety page (SoCalGas). They apply if SoCalGas is the utility at the address, so confirm the utility first.

  1. Leave the area at once and take everyone with you.
  2. From a safe place, call the gas utility (SoCalGas lists 1-800-427-2200). Call 911 if there is damage that may endanger life.
  3. Do not smoke, strike a match, switch lights or appliances on or off, or use any device that could spark.
  4. Do not try to control the leak or repair a damaged pipe or meter.

The same page lists the warning signs: the smell of gas, a hissing or whistling sound, dirt or water blowing into the air, a dry patch of grass, or a damaged appliance connection. It also warns that odor can fade, so never rely on your nose alone. Status: confirmed.

On your own job. After any gas work, check every joint with leak solution or a gas detector, and run the CO test from the safety section. If you find a leak you cannot stop right away, treat it as the steps above say: leave and call. Status: practice-based. Follow your employer's written procedure.

The math

HVAC math is a small set of ideas used again and again. Heat moves because of a temperature difference. Air and water carry heat in proportion to their flow. Electricity follows Ohm's law. Learn the ideas and the constants stop looking like magic.

You can play with most of these formulas in HVAC Math in 3D. Every worked example below was re-checked in code.

A note on trust. Items marked typical value, check the manufacturer manual or code are standard textbook or industry numbers that the research could not confirm at the primary source. Use them to learn and to sanity-check. For a real job, the nameplate, the manufacturer's data and the adopted code win.

What each constant means

Each constant is just units multiplied together. Knowing where it comes from tells you when it stops being true.

ConstantWhere it comes fromUsed for
1.0860 min/h x 0.075 lb/ft3 x 0.24 BTU/lb-FTemperature change of air (sensible heat)
4.560 min/h x 0.075 lb/ft3Total heat from an enthalpy change
0.6860 x 0.075 x 1060 BTU/lb / 7000 grains per lbMoisture change of air (latent heat)
50060 min/h x 8.33 lb/gal x 1 BTU/lb-FWater flow (hydronic heat)
12,000BTU/h in one ton of coolingConverting load to tons
3,412BTU/h in one kilowattElectric heat and efficiency

The 0.075 lb/ft3 is the density of standard air at sea level. High up, air is thinner, so 1.08 and 4.5 shrink. At 5,000 ft the density ratio is about 0.862, so the sensible constant is about 0.93. Furnaces also lose capacity at altitude. A common rule is about 4% per 1,000 ft above 2,000 ft, which gives roughly 88% at 5,000 ft (typical value, check the manufacturer manual or code).

Manual J: how big is the load?

Manual J is the ACCA method for calculating how much heating and cooling a house needs. It adds up heat leaking through the building, heat from air leakage, and heat from people and appliances. Equipment is chosen after that, never before.

Load, then equipment, then ducts, then a site test: each step feeds the nextManual J: how much heat movesArea, R-values, windows, leakage, people,design temperaturesManual S: pick equipment to fitMatch capacity and sensible heat ratio tothe load, not to the old unitManual D: size the ductsSet the friction rate, size each run,check blower CFM against static pressureVerify on siteMeasure airflow, static pressure andduct leakage, then write them downHeating and cooling loads in BTU/h,split into sensible and latentA size inside a window around the cooling load:90 to 115% (typical value, check the manual)A duct layout the blower can push air throughwithin its total external static pressureReadings on the commissioning sheet,the proof that the design workedif readings fail, revisit S or DManual J, S and D are ACCA standards; most of their tables are paywalled, so use the standard itself for job numbers.
Manual J to S to D workflow

Never size from the old unit or from square feet per ton. The load comes first, and the equipment is chosen to it. The ducts are then sized to the equipment's airflow, and readings on site tell you whether to loop back.

Conduction. Heat flows through a wall, ceiling or window in proportion to its area and the temperature difference. Insulation (R-value) slows it. U is simply 1 divided by R.

Q=U×A×ΔT=A×ΔTRtotalQ = U \times A \times \Delta T = \frac{A \times \Delta T}{R_{total}}

Example: 1,000 ft2 of R-19 ceiling has U = 0.0526. At a 70 F difference it loses 3,684 BTU/h. Change it to R-38 and the loss halves to 1,842 BTU/h. Doubling R halves the loss.

Design temperatures. Manual J does not size for the worst day on record. It uses the outdoor temperature that is exceeded only 1% of the time in summer, and 99% of the time in winter. These come from ASHRAE weather data for the nearest city. Typical indoor settings are 70 F heating and 75 F cooling. In the example city, a 99% heating temperature of 30 F gives a 40 F difference. A 1% cooling temperature of 95 F gives a 20 F difference. Manual J also adjusts the cooling number for the daily temperature swing. (Typical value, check the manufacturer manual or code.)

Air leakage. Leaks bring in outdoor air. Convert air changes per hour (ACH) to CFM, then to load with the sensible formula.

CFMinf=ACH×Volume60Q=1.08×CFMinf×ΔTCFM_{inf} = \frac{ACH \times Volume}{60} \qquad Q = 1.08 \times CFM_{inf} \times \Delta T

Example: a 1,600 ft2 house with 8 ft ceilings is 12,800 ft3. At 0.5 ACH that is 106.7 CFM, which costs about 8,064 BTU/h at a 70 F difference. A blower door test gives ACH at 50 pascals. Divide by about 15 to 20 to estimate natural leakage. With 7 ACH50 and a divisor of 17, you get 0.41 ACH. (Typical value, check the manufacturer manual or code.)

People. Manual J assumes bedrooms plus one occupants. Each gives roughly 230 BTU/h sensible and 200 BTU/h latent. A 3-bedroom house has 4 occupants: 920 sensible plus 800 latent, or 1,720 BTU/h. The exact assumptions are in the paid manual. (Typical value, check the manufacturer manual or code.)

Why rules of thumb fail. "One ton per 500 to 600 ft2" ignores insulation, glass, sun, ducts and leakage. For a 2,000 ft2 house it says 3.3 to 4 tons, or 40,000 to 48,000 BTU/h. A tight, well-insulated house may calculate 22,000 BTU/h, which is 1.83 tons, so a 2-ton unit. The rule would overshoot by 82% to 118%. Oversizing causes short cycling, poor humidity control and uneven rooms.

Manual S: picking the equipment

Manual S matches real equipment to the Manual J load. You do not use nominal tons. You use the manufacturer's expanded performance data at your actual indoor wet-bulb and outdoor dry-bulb temperature. The sensible capacity must cover the sensible load, and the latent capacity must cover the latent load.

Capacityallowed=Load×(min%…max%)Capacity_{allowed} = Load \times (\text{min\%} \ldots \text{max\%})

Manual S limits how far equipment may exceed the load. Only two figures were found, both from a 2009 ACCA-staff article: 115% of the cooling load for an air conditioner and 140% of the heating load for a furnace. Limits for heat pumps are unconfirmed from ACCA's own pages. (Typical value, check the manufacturer manual or code.)

Example: with a 30,000 BTU/h cooling load, an air conditioner may go up to 115%, which is 34,500 BTU/h or 2.88 tons. A 3-ton unit whose real capacity at your conditions is 34,500 BTU/h sits exactly at 115%. That is the top of the limit, not over it. It passes, but it leaves no margin. A 2.5-ton unit also fits. Never round up just to be safe.

The sensible heat ratio (SHR) is the share of the cooling load that is temperature rather than moisture.

SHR=QsensibleQtotalSHR = \frac{Q_{sensible}}{Q_{total}}

Example: 21,000 sensible plus 9,000 latent is 30,000 total, so SHR = 0.70. Comfort cooling usually lands between 0.70 and 0.80. Pick a coil whose SHR matches the house.

Manual D: sizing the ducts

Manual D sizes ducts so the blower can push the right airflow. The blower has a fixed pressure budget. Spend part of it on the filter, coil and grilles. Spread what is left over the longest duct run.

FR=ASP×100TEL,ASP=TESPrated−∑ΔPcomponentsFR = \frac{ASP \times 100}{TEL}, \qquad ASP = TESP_{rated} - \sum \Delta P_{components}

FR is the friction rate in inches of water column (in wc) per 100 ft. ASP is the available static pressure. TEL is the total effective length: straight duct plus the equivalent length of every fitting, on supply and return, for the longest run.

Example: a blower rated for 0.50 in wc, with 0.20 used by components, leaves 0.30. If the longest run has TEL = 300 ft, then FR = 0.30 x 100 / 300 = 0.10 in wc per 100 ft. Fitting lengths come from the Manual D tables. A sample of 50 ft straight, three elbows at 30 ft and two boots at 15 ft totals 170 ft (typical values, check the manufacturer manual or code).

Speed and size. Air speed is CFM divided by duct area. Pressure from motion is the velocity pressure.

V=CFMA,VP=(V4005)2V = \frac{CFM}{A}, \qquad VP = \left(\frac{V}{4005}\right)^2

Example: 400 CFM in an 8 in round duct. Area is 0.3491 ft2, so V is 1,146 fpm and VP is 0.0819 in wc. Typical residential targets are 700 to 900 fpm in trunks and 500 to 700 fpm in branches (typical values, check the manufacturer manual or code).

Friction in round duct. A common fit for galvanized steel:

ΔP100 ft=0.109136×Q1.9D5.02\frac{\Delta P}{100\,ft} = \frac{0.109136 \times Q^{1.9}}{D^{5.02}}

Q is CFM and D is diameter in inches. For 400 CFM in 8 in, friction is 0.281 in wc per 100 ft. To hold 0.08, you need D = 10.27 in. Notice D sits to the fifth power. A slightly bigger duct cuts friction a lot. This fit is widely quoted but not checked against the handbook (typical value, check the ASHRAE Fundamentals handbook).

Rectangular duct. A rectangle and a round duct are equal when they have the same friction at the same airflow, not the same area.

De=1.30 (a b)0.625(a+b)0.25D_e = \frac{1.30 \, (a \, b)^{0.625}}{(a + b)^{0.25}}

Example: a 12 x 6 in duct has De = 9.14 in. The matching round duct has an area of 65.6 in2, which is less than the rectangle's 72 in2. The round shape moves air more efficiently, so it needs less area.

Fan laws. Change the fan speed and airflow changes in proportion. Pressure changes with the square, and power with the cube.

CFM2=CFM1N2N1,SP2=SP1(N2N1)2,HP2=HP1(N2N1)3CFM_2 = CFM_1\frac{N_2}{N_1}, \quad SP_2 = SP_1\left(\frac{N_2}{N_1}\right)^2, \quad HP_2 = HP_1\left(\frac{N_2}{N_1}\right)^3

From 800 to 1,000 rpm: airflow goes from 1,200 to 1,500 CFM, pressure rises 1.56 times and power rises 1.95 times. Restrictive ducts cost airflow fast, and extra speed costs a lot of power.

Measured pressure. Total external static pressure (TESP) is the return suction plus the supply pressure, both as positive numbers.

TESP=∣Preturn∣+PsupplyTESP = |P_{return}| + P_{supply}

Example: supply 0.38 and return -0.32 gives 0.70 in wc. If the unit is rated for 0.50, the duct, filter or coil is too restrictive.

The airflow and heat equations

All the air formulas share one shape: a constant, times CFM, times a change.

Qsensible=1.08×CFM×ΔTQ_{sensible} = 1.08 \times CFM \times \Delta T
Qlatent=0.68×CFM×Δgrains,grains=7000×WQ_{latent} = 0.68 \times CFM \times \Delta grains, \qquad grains = 7000 \times W
Qtotal=4.5×CFM×(hin−hout)Q_{total} = 4.5 \times CFM \times (h_{in} - h_{out})
Qwater=500×GPM×ΔTQ_{water} = 500 \times GPM \times \Delta T

Common mistakes: using 1.08 for moisture, using the room temperature difference instead of the supply-minus-return difference, and forgetting altitude. These constants are typical values, check the manufacturer manual or code.

Temperature split

The split is return air temperature minus supply air temperature on cooling. It follows from airflow and the sensible load. Design airflow is about 400 CFM per ton, and California verification uses 350.

CFM=tons×400,ΔTsplit=Qsensible1.08×CFMCFM = tons \times 400, \qquad \Delta T_{split} = \frac{Q_{sensible}}{1.08 \times CFM}

Example: a 3-ton system at 400 CFM per ton moves 1,200 CFM. At SHR 0.75, sensible capacity is 0.75 x 36,000 = 27,000 BTU/h, so the split is 20.8 F. At 350 CFM per ton (1,050 CFM) the split rises to 23.8 F. Less air means a bigger split and a colder coil. (Typical value, check the manufacturer manual or code.)

Superheat and subcooling

Refrigerant boils at a temperature that depends on pressure. A pressure-temperature (PT) chart converts a gauge reading to that saturation temperature. Add 14.696 to gauge pressure to get absolute pressure. Superheat and subcooling measure how far the real line temperature is from saturation.

Superheat=Tsuction line−Tsat(Psuction)Superheat = T_{suction\,line} - T_{sat}(P_{suction})
Subcooling=Tsat(Pliquid)−Tliquid lineSubcooling = T_{sat}(P_{liquid}) - T_{liquid\,line}

These PT values were computed with the open-source CoolProp library:

Refrigerant40 F (psig)100 F (psig)
R-410A118.4317.6
R-2268.6195.9
R-32121.0325.7
R-32 reads slightly above R-410A and R-454B below it, at both 40 F and 100 FSaturation pressure in psigR-410A at 40 F: 118.4 psig (CoolProp)118.4R-410AR-32 at 40 F: 121.0 psig (CoolProp)121.0R-32R-454B at 40 F: 107-112 psig (Secondary sources, range)107-112R-454BR-410A at 100 F: 317.6 psig (CoolProp)317.6R-410AR-32 at 100 F: 325.7 psig (CoolProp)325.7R-32R-454B at 100 F: 291-301 psig (Secondary sources, range)291-301R-454BAt 40 FAt 100 FSolid bars: computed with CoolProp. Dashed bar with whisker: R-454B range from secondary sources (bubble versus dew point).Dashed line: the R-410A level, for comparison. R-454B is not in CoolProp, so check the manufacturer chart.
Saturation pressures of R-410A, R-32 and R-454B

At the same temperature R-32 sits 2 to 3% above R-410A, while the whole R-454B range sits below it. A chart for the wrong refrigerant therefore gives a wrong saturation temperature.

Example, superheat: R-410A suction at 118 psig saturates near 40 F. A suction line at 52 F gives 12 F of superheat. Example, subcooling: R-410A at 317 psig saturates at 100 F. A liquid line at 90 F gives 10 F of subcooling.

Use superheat to charge fixed-orifice systems and subcooling to charge TXV or EEV systems. Targets (one Daikin Comfort chart lists 8 F, and Carrier lists 5 to 11 F by size) vary by model, so follow the manufacturer's chart or nameplate. R-454B was not in the library, so check its chart from the manufacturer. Blends such as R-410A glide slightly.

Psychrometrics

Psychrometrics is the math of air plus water vapor. Three numbers matter most.

Dew point is the temperature where air becomes saturated. A surface colder than that sweats. The Magnus formula (T and dew point in C; a = 17.625, b = 243.04):

Td=b γa−γ,γ=ln⁡RH100+a Tb+TT_d = \frac{b \, \gamma}{a - \gamma}, \qquad \gamma = \ln\frac{RH}{100} + \frac{a \, T}{b + T}

At 75 F and 50% RH, the dew point is 55.1 F.

Wet-bulb is the temperature of a wet thermometer in moving air. Equipment ratings are listed against indoor wet-bulb, with 67 F as the standard. The Stull fit (T in C, RH in percent):

Tw=Tarctan⁡ ⁣[0.151977RH+8.313659]+arctan⁡(T+RH)−arctan⁡(RH−1.676331)+0.00391838 RH1.5arctan⁡(0.023101 RH)−4.686035T_w = T \arctan\!\big[0.151977\sqrt{RH + 8.313659}\big] + \arctan(T + RH) - \arctan(RH - 1.676331) + 0.00391838\,RH^{1.5}\arctan(0.023101\,RH) - 4.686035

At 75 F and 50% RH, wet-bulb is 62.7 F.

Enthalpy is the total energy in a pound of dry air, sensible plus latent.

h=0.240 T+W (1061+0.444 T)h = 0.240\,T + W\,(1061 + 0.444\,T)

At 75 F and 50% RH, the humidity ratio is W = 0.0092 lb water per lb dry air. That is about 64.4 grains (7,000 x 0.0092). Then h = 0.240 x 75 + 0.0092 x (1061 + 33.3) = 28.1 BTU/lb. The coil's real job is to move enthalpy, not only temperature. These formulas are standard fits (typical values, check the ASHRAE handbook or a psychrometric chart).

Furnace firing and temperature rise

Input is the gas energy burned each hour. Output is the heat delivered to the air. AFUE is the efficiency averaged over a season.

Output≈Input×AFUEOutput \approx Input \times AFUE

Example: an 80,000 BTU/h input at 96% AFUE delivers about 76,800 BTU/h. An 80% unit delivers 64,000. Steady-state efficiency differs a little from AFUE.

The nameplate lists an allowed temperature rise, such as 25 to 55 F. Rise is supply minus return on heating.

ΔTrise=Output1.08×CFM\Delta T_{rise} = \frac{Output}{1.08 \times CFM}

Example: 76,800 BTU/h of output into 1,200 CFM gives a 59.3 F rise. That is high, so airflow is too low. For a 50 F rise you need 1,422 CFM. Too high a rise means too little air. Too low a rise means too much air or low fire.

Checking the firing rate. Time the gas meter dial.

CFH=3600×ft3seconds,Input=CFH×heating valueCFH = \frac{3600 \times ft^3}{seconds}, \qquad Input = CFH \times \text{heating value}

Example: 1 ft3 in 36 seconds is 100 CFH. At 1,030 BTU/ft3 that is 103,000 BTU/h. Compare with the nameplate, and set manifold pressure to the nameplate value. Natural gas is commonly about 3.5 in wc and propane about 10 in wc (typical values, check the manufacturer manual or code).

Gas piping and venting. Pipe sizing comes from the code tables for the longest run and the total load. Do not guess it from a formula. Vent sizing is also table driven (NFPA 54 or the IFGC). Condensing furnaces use sealed PVC pitched back toward the furnace. Use the adopted code and the manufacturer's instructions for both. Combustion air has its own code rules too.

Electrical

Ohm's law. Voltage pushes current through resistance, and power is voltage times current.

V=IR,P=VI=I2R,1 kW=3412 BTU/hV = I R, \qquad P = V I = I^2 R, \qquad 1\,kW = 3412\,BTU/h

Example: a 240 V supply across a 12 ohm element draws 20 A. Power is 4,800 W, which is 16,378 BTU/h. A 10 kW strip heater makes 34,120 BTU/h and draws 41.7 A at 240 V.

Three phase. Commercial units use it. Power uses the square root of 3 and line-to-line voltage.

P=3×VLL×I×PF,imbalance %=max deviation from averageaverage×100P = \sqrt{3} \times V_{LL} \times I \times PF, \qquad \text{imbalance \%} = \frac{\text{max deviation from average}}{\text{average}} \times 100

Example: 208 V, 20 A, power factor 0.85 gives 6,125 W. Legs at 205, 208 and 213 V average 208.7 V. The worst leg is 4.3 V off, so imbalance is 2.08%. Keep it under 2% (typical value, check the manufacturer manual or code).

MCA and MOCP. MCA is the minimum circuit ampacity, the smallest wire. MOCP is the maximum overcurrent protection, the largest breaker or fuse. Both are printed on the nameplate, so use those.

MCA=1.25×RLAlargest+∑Iothers,MOCP=1.75×RLAcompressor+∑IothersMCA = 1.25 \times RLA_{largest} + \sum I_{others}, \qquad MOCP = 1.75 \times RLA_{compressor} + \sum I_{others}

Example: compressor RLA of 18 A and a fan at 1.5 A give MCA = 1.25 x 18 + 1.5 = 24.0 A. MOCP is 1.75 x 18 + 1.5 = 33.0 A, and you round down to a 30 A breaker. Never round up, and never size the breaker to MCA. The 125% and 175% factors were confirmed in a trade source, Electrical Construction and Maintenance, not in the NEC text. Check the nameplate and the adopted NEC.

Capacitors. The microfarad value can be estimated from current and voltage.

C[μF]=2652.6×IV(60 Hz)C[\mu F] = \frac{2652.6 \times I}{V} \quad (60\,Hz)

Example: 7.2 A measured at 370 V gives 51.6 uF. Compare with the rating on the can. Tolerance is usually plus or minus 6% (typical value, check the manufacturer manual or code).

Efficiency ratings

COP, EER, SEER2 and HSPF2 are the same idea, useful heat or cooling out divided by electricity in, at different test conditions.

EER=3.412×COP,COP=heat outelectricity inEER = 3.412 \times COP, \qquad COP = \frac{\text{heat out}}{\text{electricity in}}

SEER2, EER2 and HSPF2 replaced SEER, EER and HSPF under a newer federal test method (Appendix M1), confirmed in the Federal Register notice. Do not compare an old SEER number directly with a SEER2 number. A COP of 3 is not 300% efficient. It moves three units of heat for one unit of electricity. Use EER2 for peak power and SEER2 for yearly energy. The exact conversion factors between old and new ratings are typical values, check the manufacturer manual or code.

Fuel cost comparison: divide the price per unit by the energy delivered.

$MMBtu=price per unitBTU per unit×efficiency×1,000,000\frac{\$}{MMBtu} = \frac{\text{price per unit}}{BTU\ per\ unit \times efficiency} \times 1{,}000{,}000

With made-up prices: gas at $1.80 per therm and 96% AFUE costs $18.75 per MMBtu. Resistance heat at $0.28 per kWh costs $82.06. A heat pump with COP 3 costs $27.35. Prices are illustrative only.

ASHRAE 62.2 ventilation

The standard sets whole-house mechanical ventilation for indoor air quality. It has a floor-area term and an occupant term.

Qtot=0.03×Afloor+7.5×(Nbr+1)Q_{tot} = 0.03 \times A_{floor} + 7.5 \times (N_{br} + 1)

Example: 2,000 ft2 with 3 bedrooms gives 0.03 x 2,000 + 7.5 x 4 = 90 CFM. An infiltration credit may lower it. The formula is confirmed by ACCA's 62.2 update post. Local exhaust rates, such as 100 CFM intermittent for a kitchen and 50 CFM for a bath, are typical values, check the manufacturer manual or code.

California Title 24 numbers

California requires measured, third-party (HERS) verification of ducts, airflow, fan power and charge on many installs. These are pass or fail limits. The numbers below were confirmed at energy.ca.gov. The 2025 code cycle takes effect Jan 1, 2026.

Example: a 3-ton unit needs at least 1,050 CFM. At 0.45 W/CFM the fan may use 472.5 W, or about 473 W. At 0.58 W/CFM it may use 609 W. Common errors: skipping the HERS rater, testing only the supply side, and using values from the wrong code year.

Quick recap

Scenes to open. Each part of the math section has matching scenes in HVAC Math in 3D:

Part of this sectionScenes
The airflow formulas, sensible and latent heatHow much heat the air carries; Cooling coil: sensible plus latent; Moisture is heat too; Airflow per ton and the temperature split; Hot water: 500 × gallons × temperature drop
Manual J: conduction, leakage, rule of thumbDesign temperatures: how big is ΔT?; Heat leaking through a ceiling; Air leaking in and out; Rule of thumb vs a real load calculation; Build your house: Manual J-lite; Manual S: does the equipment fit the load?
Ducts, friction, static pressure and fan lawsDuct speed, friction and size; Rectangular duct, round equivalent; Static pressure: what the blower pushes against; Fan laws: speed up a little, pay a lot; Equivalent length: what fittings add
Superheat, subcooling, PT and evacuationSuperheat: how far past boiling; Subcooling: how far past condensed; Pressure and temperature go together; Evacuation and pressure test: the method
PsychrometricsDew point and wet bulb; Humidity ratio and enthalpy; The psychrometric chart: drag the air
Furnace, gas clocking and combustion airFurnace input, output and temperature rise; Clocking the gas meter; Combustion air for a closet; Venting: rise to the chimney, fall to the furnace
ElectricalVolts, amps, watts and BTU: a heat strip; Wire and breaker: MCA and MOCP; Is the run capacitor still good?; Three-phase power: √3, balance and rotation
Efficiency, fuel cost, ventilation and Title 24COP, EER and HSPF2: heat for every watt; What a million BTU costs by fuel; Whole-house ventilation, ASHRAE 62.2; California Title 24: airflow, fan watts, leakage

Tools and instruments

Every tool below does one job in the install, service or test chain. Each group has a table: the tool, what it does, the one master secret, and what to buy. Prices are rough. Where a number could not be confirmed, it says "typical value, check the manufacturer manual." The manufacturer's manual and local code always win.

Tubing and flaring

ToolWhat it doesMaster secretWhat to buy
Tubing cutterCuts copper tube square with a roller wheelA square cut makes a good flare and a tight brazeImperial or Ridgid constant-tension cutter, plus spare wheels
Reamer / deburrerRemoves burrs inside and outside the cutReam until smooth, not until the wall gets thinCombination reamer
Flaring toolForms a 45-degree flare on the tube endUse an eccentric cone tool; it takes less force and flares betterYellow Jacket or Imperial eccentric tool, about $80-150
Torque wrenchClicks at a set torque for flare nutsHold the backing wrench at 90 degrees to the torque wrench1/2 in drive click type, plus a 3/8 in drive for valve work
Swaging toolExpands tube so same-size tube slides inAnneal hard copper first or it splitsLever-type kit (Imperial, Mastercool, Rothenberger)
Tube benderBends tube without kinkingBend a little past the angle, then relaxLever bender for 1/4 to 7/8 in, plus spring benders
Pinch-off toolSqueezes a small tube shutSmall tubes only; never a permanent sealLever or hydraulic pinch-off

Flare nut torque depends on brand and size, so read the unit's manual. Across 13 brands, 3/8 in flares mostly list 24-31 ft-lb. The 1/4 in size runs about 10-13 ft-lb, 1/2 in about 36-46, and 5/8 in about 45-60. That reading comes from an unlabeled sticker, so treat it as an inference. Lubricant changes torque, so stay on the low side if the threads are oiled. Follow the manual on flare lubricant: the Daikin R-32 manual says no refrigeration oil on the flare or threads. Minimum bend radius of about 5 times the tube diameter is a typical value, check the manufacturer manual.

Brazing and nitrogen

ToolWhat it doesMaster secretWhat to buy
Brazing torch kitHeats joints to braze temperatureHeat the tube first, then the fitting; filler follows heatAir-acetylene kit for line sets, oxy-acetylene for big pipe
Filler rod and fluxJoins copper (and copper to brass or steel)Phos-copper needs no flux on copper to copper; use silver and flux on brass or steel15% silver rod, plus flux
Nitrogen regulator and flowmeterPurges air from the pipe and sets flowFlow and pressure are different thingsHarris or Uniweld, 0-400 psi regulator, 0-15 SCFH flowmeter
Pressure test setupPressurizes the system to find leaksCorrect for temperature before calling a leakSame regulator, plus a digital gauge that compensates
Heat shield, rags, extinguisherProtects valves and nearby partsHeat paste or wet rags on valve coresHeat shield, plus a Class B dry powder extinguisher for A2L work

BCuP-5 melts between 1,190 and 1,475 F. Acetylene may not be used above 15 psig, and the cylinder valve opens no more than 1.5 turns, preferably 3/4. Leave the cylinder wrench on the stem. The flow tool is fed at 50-60 psi, but that is not the pressure inside the copper.

Vacuum and micron gauge

ToolWhat it doesMaster secretWhat to buy
Vacuum pumpPulls air and moisture out of the circuitFresh oil matters mostTwo-stage pump with an explicit A2L or spark-free label
Micron gaugeReads deep vacuum in micronsPut it at the far end, away from the pumpAny gauge that logs to an app
Core removal toolPulls Schrader cores under pressureCores out means a much faster pullYellow Jacket or Fieldpiece style tool
Large-bore hosesShort fat hoses to speed evacuationFewer adapters, shorter hoses3/8 in hoses (typical value, check the manufacturer manual)

The usual target is 500 microns or lower. Water boils at 1 F at 1,000 microns and at -12 F at 500 microns. Pump size of 5-6 CFM two-stage for homes is a typical value, check the manufacturer manual. Manifold gauges cannot read this range. Each manufacturer sets its own target and decay limit (see the manufacturer table in Installation).

Gauges and charging

ToolWhat it doesMaster secretWhat to buy
Analog manifoldShows low and high refrigerant pressureZero it first and use low-loss couplersA set that lists R-32 and R-454B, reading to 800 psi
Digital manifoldReads pressure and line temperature, then does the mathInsulate the line clampsTesto 550s/557s or Fieldpiece SMAN (check the label for A2L)
Pipe clamp thermometersRead line temperature for superheat and subcoolingClamp near the service valveFieldpiece clamps
Refrigerant scaleWeighs refrigerant in and outWeigh in the charge on new installsWireless scale from Yellow Jacket, Fieldpiece or Inficon
Pressure-temperature chart or appTurns pressure into saturation temperatureUse bubble and dew values for blendsFree apps from Fieldpiece, Testo or Danfoss

Reference points: R-410A saturates at 118.4 psig at 40 F and 317.6 psig at 100 F. R-454B runs about 107-112 psig at 40 F and 291-301 psig at 100 F.

Recovery

ToolWhat it doesMaster secretWhat to buy
Recovery machineMoves refrigerant into a cylinderPush-pull for liquid on big systems; chill the cylinderFieldpiece MR45 or Appion G5Twin for A2L; Yellow Jacket RecoverXLT 95760 for R-410A and R-22
Recovery cylinderStores recovered refrigerantKeep one cylinder per refrigerant30 lb DOT cylinder (Worthington, Mastercool)
Refrigerant identifierChecks what is in an unknown cylinderTest before you recoverMastercool or Robinair

Leak detection

ToolWhat it doesMaster secretWhat to buy
Electronic detectorAlarms when it senses refrigerantInfrared sensors last longer and give fewer false alarmsFieldpiece DR82 or UEI RLD15B, both A2L
Bubble solutionShows bubbles at a leakUse a non-corrosive refrigerant-rated mixBig Blue or similar
UV dye and lampMarks a slow leak in the oilUse dye approved for the refrigerant and oilTracer or Spectronics kit
Gas leak detectorFinds natural gas and propane leaksSniff first, then confirm with bubblesBacharach or Testo

Electrical meters

ToolWhat it doesMaster secretWhat to buy
MultimeterVolts, ohms, continuity, microfarads, temperatureLive-dead-live: test on a known source before and afterFluke 117 or Fieldpiece HS36, CAT III 600 V
Clamp meterReads current without breaking the wireClamp one wire onlyFluke 324, Fieldpiece or Klein CL800
Capacitor testerMeasures run and start microfaradsMatch microfarads and use equal or higher voltageFieldpiece, Klein, or a meter with a capacitance range
Voltage testerDetects AC voltageUse a solenoid tester when ghost voltage fools youKlein NCVT-3 or Fluke 1AC
MegohmmeterTests winding insulation to groundCareful on hermetic compressorsFieldpiece SMX or Fluke 1507

Flame sensor current of about 0.5 to 7 microamps is normal on one brand's tech tip, typical value, check the manufacturer manual. The Fluke 116 reads down to 0.1 microamp.

Airflow and pressure

ToolWhat it doesMaster secretWhat to buy
Digital manometerReads small pressures in inches of waterRe-zero it before each readingTesto 510i, Fieldpiece SDMN5 or Dwyer Magnehelic
Static pressure kitProbes for supply and return ductsAdd the two readings as absolute valuesDwyer tip kit
Flow hoodReads register airflow directlyCompare the total to about 350-450 CFM per ton (typical value, check the manufacturer manual)Testo 420 or Fieldpiece
Anemometer and pitot tubeMeasure air speed in a ductTake a traverse, not one pointTesto 417 or Fieldpiece STA2
Psychrometer and thermometersMeasure dry bulb, wet bulb and humidityIR sees surfaces only; use contact probes on pipesTesto 605i or Fieldpiece

Total external static pressure target is 0.5 in. w.c. or less. Trouble starts at 0.8 or higher on most newer homes. Run the blower on high, wait about 3 minutes, then read.

Combustion

ToolWhat it doesMaster secretWhat to buy
Combustion analyzerReads O2, CO, stack temperature and draftAlways read CO air-freeTesto 310/320 or Fieldpiece
Personal CO monitorWarns you of CO35 ppm matches the NIOSH limit; setpoints vary by modelFieldpiece or Testo

Air-free CO equals measured CO times 20.9, divided by (20.9 minus O2). So 100 ppm at 14% O2 is over 300 ppm air-free. Do not tune to the 400 ppm certification limit. A healthy furnace reads under 50 ppm air-free. Replace sensors on schedule: O2 cells about 2-3 years, CO sensors 3-5 years (one source).

Ducts

ToolWhat it doesMaster secretWhat to buy
Aviation snipsCut sheet metalCarry two; left, right and straight cover almost everythingKlein set (red left, green right, yellow straight)
Crimper and seamersShape and join ductIf it skips, the duct is out of roundHand crimper and seamer pair
Mastic, foil tape, caulk gunSeals jointsMastic stays airtight longer than tape or caulkUL 181 foil tape, water-based mastic, mesh tape
Duct blasterPressurizes ducts to 25 Pa to measure leakageTest at rough-in, before drywallRetrotec or Energy Conservatory

IECC 2012 allows total duct leakage of 4 CFM25 per 100 sq ft after construction. Later editions need checking.

Drains

ToolWhat it doesMaster secretWhat to buy
Wet/dry vac and flush kitClears algae from drain linesSlope the line at 1/4 in per footVac with a drain adapter, plus coil-safe tablets
Condensate pump and float switchLifts water to a drain and cuts power on overflowA sloped discharge often makes the check valve unnecessaryLittle Giant VCMX/VCMA with a safety switch

Power tools

ToolWhat it doesMaster secretWhat to buy
Cordless drill and impact driverDrives screws, drills holesImpact driver for lags, drill for plasticMilwaukee M18 FUEL or DeWalt 20V
SDS hammer, hole saws, recip sawCuts holes through walls and framingCut from the least important face firstSDS-plus hammer, bi-metal and carbide saws
Nut drivers and insulated screwdriversPanels, duct screws, live workLow clutch stops strippingKlein or Milwaukee magnetic set; Klein or Wiha VDE set

PPE and ladders

ToolWhat it doesMaster secretWhat to buy
Safety glasses and face shieldBlock debris, heat and refrigerantAnti-fog matters under a respiratorZ87+ wraparound glasses
GlovesCut, heat and cold protectionThin pair in the pouch, heavy pair on the truckA4 cut-level nitrile gloves, leather brazing gloves
Respirator and hearing protectionDust, mold and noiseRespirator first, then glasses3M half-face with P100 filters, foam plugs
Ladders and fall protectionSafe access to roof and atticLevel the ladder; set the anchor before stepping offFiberglass Type IA ladders, full-body harness
Appliance dollyMoves furnaces and condensersStrap through the frame, not the coil finsRated dolly; stair-climbing model for stairs

The corrections that matter

Several figures in older notes were wrong. These are the fixed versions.

Recovery level. For a high-pressure appliance under 200 lb of charge, the required recovery level is 0 in. Hg. The 10 in. Hg figure applies only at 200 lb or more, and only for equipment made after November 15, 1993. Older equipment at 200 lb or more is 4 in. Hg. The rule is 40 CFR 82.156 Table 1. If leaks prevent it, recover to the lowest level you can reach.

Nitrogen flow. Purge flow is about 20-50 SCFH. Brazing flow is about 2-3 SCFH. One source gives a wider 2-5 SCFH range. Too much flow cools the joint and hurts penetration. A full nitrogen cylinder reads 2,000 to 2,640 psig at 70 F depending on cylinder type, so always use a regulator (Nippon Sanso). One pipe volume of nitrogen is not proof the air is gone, so time the purge from the real flow.

Flare torque. For 3/8 in flares, most brands list 24-31 ft-lb. An older note of 20-30 ft-lb was too low. Use the manual for your unit.

Capacitors. A new run capacitor is held to plus or minus 6% of its rating. In service, many shops replace one that reads more than 10% low under load. Some shops use 5-6%. Always replace the run capacitor when you replace a PSC motor.

A2L recovery machine. The A2L-rated machine to name is the Fieldpiece MR45. It is rated for R-32, R-454B and R-1234yf, and costs about $1,150. It auto-stops at 0 psig by default.

Temperature and nitrogen tests. A pressure change of about 0.3 psi per degree F is normal at 150 psig. An older rule of 1 psi per 5 F was off at that pressure.

Unconfirmed items. Anything labeled "typical value, check the manufacturer manual" was not checked against a manufacturer document. Model numbers marked unverified in the research notes were left out of the picks.

Local compliance kit (practice-based). Carry a tape or laser measure for the 5 ft Zone 0 and the setback checks, and a level for the pad. Add a sound-level meter set to dBA to record the condenser at the property line: the County has no confirmed equipment limit, and the City's 53 dBA is CITY OF SANTA BARBARA ONLY. Take before and after photos of the pad and screening, keep the County permit card on site, and check the parcel's climate zone in the CEC lookup on your phone.

Sources used: Fieldpiece for meters and recovery, ACCA blog on 500-micron vacuum, HVAC School on target superheat, and the DOE duct leakage FAQ.

Scenes to open. Every group of tools above is animated step by step in HVAC Tools in 3D: Safety: Protect your eyes, hands, lungs and ears; Ladder angle and fall arrest on a roof. Hand tools and drilling: Panel, terminal, wire and valve: the hand tools; Scan, pilot, cut and sleeve: drilling a line set penetration. Tubing: Cut, ream, swage, bend and pinch copper tube; Make a flare, then torque the nut. Brazing and nitrogen: Braze a copper joint safely; Nitrogen purge: purge flow versus braze flow; Nitrogen pressure test and temperature drift. Vacuum: Set up the vacuum: pump, large hoses, cores out; Micron gauge: pull down, isolate, watch the rise. Gauges, recovery and leaks: Read the gauges: pressure to saturation temperature; Recover refrigerant: machine, cylinder and scale; Find a leak: electronic, bubbles or UV dye. Gas and combustion: Gas pipe: wrench, back-up wrench and leak check; Combustion analyzer: air-free CO, O2 and stack temperature. Electrical: Lock out, then prove it is dead: tester, meter and 24 V; Clamp meter: amps against the nameplate; Capacitor, megohm and burnout checks. Air side: Static pressure: supply plus return is the TESP; Measure airflow: pitot, anemometer and flow hood; Delta T: supply and return temperature. Duct work: Snips, crimper and brake: cut and shape duct; Seal the duct, then test the leakage. Drain: Clear and pump the condensate drain.

Installation

This is a split-system install (outdoor condenser or heat pump, indoor coil or air handler) in the order a careful crew does it. Each step has the reason behind it. Where values differ by brand, a table is shown. In every such case, use the manufacturer's installation manual. Safety first: lock out power, discharge capacitors, and hold an EPA 608 certification to buy or handle refrigerant. Never use oxygen or compressed air to test pressure. A2L refrigerants (R-454B, R-32) are mildly flammable, so use A2L-rated tools and keep ignition sources away.

  1. Set the equipment. Place the outdoor unit on a level pad with the clearances in the manual. Set the indoor unit level, or sloped as the manual says for the drain. Check that the breaker and disconnect match the unit's MCA and MOCP numbers.
    • Why: a tilted unit drains badly and strains the compressor. Poor clearance starves the coil of air and makes every later reading harder to trust.
    • Local rules (Montecito). Open the County permit before you change a unit, because the County exempts only a swap of component parts. Set the condenser on a non-combustible pad and keep wood pads, plastic covers, combustible screens and mulch out of the 5 ft next to the house. Raise the pad if the parcel has flooded, and place or buffer the unit away from neighbors. Moving the condenser, adding a rooftop unit or running a visible line set needs a written Director determination first. See Montecito and Santa Barbara: your local rules.
  2. Run the line set. Size the suction and liquid lines per the manufacturer. A common 3-ton example is 3/4 in suction and 3/8 in liquid, but this is a typical value, check the manufacturer manual.
    • Use clean, capped ACR copper and keep tube ends capped until you braze.
    • Insulate the suction line. Support it every 4-5 feet, avoid kinks, and keep it off metal framing with isolators.
    • Keep total length within the maximum.
    • Why: dirt and moisture inside the tube ruin a system. Bare suction line sweats. Metal contact wears through the copper over time.
  3. Braze with nitrogen flowing. Confirm the system is open to atmosphere through a port or open end, never a sealed pressure.
    • Flow regulated nitrogen through the line while you braze. The brazing flow is about 2-3 SCFH, low enough not to cool the joint. A purge before lighting runs about 20-50 SCFH.
    • Clean the pipe with abrasive cloth. Use 15% silver rod (BCuP-5) without flux for copper to copper. Use silver rod with flux for copper to brass or steel.
    • Heat the tube first, then the fitting, and touch the rod to the joint away from the flame.
    • Protect valves and the expansion valve with a heat shield or wet rag, and follow the manual on removing Schrader cores.
    • Why: without nitrogen, black scale forms inside the tube and later clogs the metering device and fouls the oil.
  4. Pressure test with nitrogen. Set the regulator so you never exceed the lowest-rated part on the system. Raise pressure in steps and check joints with bubble solution. Then hold and watch the gauge. The numbers differ by manufacturer, so use the manufacturer's installation manual.
    • Test pressure is not universal. Manufacturer manuals run from 160 psig (Lennox) to 604 psi (Daikin R-32 mini-split). See the manufacturer table after this list.
    • The hold time runs from 15 minutes (Goodman, Rheem) to 1 hour (Trane, Carrier) to 24 hours (Fujitsu).
    • Use the manufacturer's installation manual for the test pressure and hold. Never exceed the lowest-rated part.
    • Correct for temperature: P2 = T2 x P1 / T1, with pressure in psia and temperature in degrees Rankine. As an example, 150 psig at 80 F drops to about 146.95 psig at 70 F with no leak, so about 0.3 psi per degree F. A digital gauge with a probe does this for you.
    • Why: finding a leak now costs minutes. Finding it after charging costs refrigerant and a return trip.
  5. Evacuate. Remove the Schrader cores with a core removal tool. Use 3/8 in or larger hoses and a pump rated for the refrigerant (A2L-rated if you work with R-32 or R-454B). Put the micron gauge on a separate port, ideally at the far end of the system, and use fresh pump oil. Pull to 500 microns or lower. ACCA confirms 500, and HVAC School and EPA GreenChill pull to 300, so deeper is better. Then close the valve to the pump and watch the decay. The pass line differs by manufacturer, so use the manufacturer's installation manual:
    • ACCA: stay under 1,000 microns for 5 minutes.
    • Building Science Corporation: 700 microns or less in 10 minutes, from a 300 micron start.
    • EPA GreenChill: 100 microns or less drift over 24 hours.
    • Manufacturers set their own pass line: Trane allows a rise of 500 microns in 1 minute and 1,500 in 10 minutes, Carrier 1,500 in 10 minutes, and Lennox no rise above 500 within 20 minutes. See the manufacturer table.
    • A rise that levels off means moisture is still boiling off, so keep pumping. A steady climb to atmosphere means a leak.
    • For a wet or contaminated system, use a triple evacuation: pull down, break the vacuum with nitrogen to a few psig, then pull again.
    • Why: water boils at 1 F at 1,000 microns, so only a deep vacuum removes moisture. Moisture and air inside the system make acid and block the metering device.
  6. Charge. Start with weigh-in, then verify.
    • Weigh-in. The condenser nameplate gives a factory charge for a set line length (often 15 ft, check the nameplate). Add refrigerant by weight for extra line. The oz-per-foot figure depends on the liquid line size and brand. For a 3/8 in liquid line, manufacturers list 0.47 oz/ft (Trane) to 0.60 oz/ft (Carrier, Rheem), so use the manufacturer's installation manual. One mini-split brand (Pioneer, R-454B) lists 0.11 oz/ft beyond 25 ft. Use a scale that resolves half an ounce.
    • Superheat. This is for fixed-orifice or piston systems. Take suction pressure, convert it to saturation temperature, and subtract it from the suction line temperature measured about 6 in from the compressor. The target comes from the manufacturer's chart using indoor wet bulb and outdoor dry bulb (confirmed by HVAC School). A "typical 8-20 F" range is unconfirmed, so it is a typical value, check the manufacturer manual. The California Energy Commission passes a unit within plus or minus 5 F of the chart target.
    • Subcooling. This is for TXV systems. Subtract the liquid line temperature from the condensing saturation temperature. The target is on the nameplate. A "typical 8-12 F" is unconfirmed, so it is a typical value, check the manufacturer manual. California passes a unit within plus or minus 3 F.
    • Conditions. Run the system until stable, about 15 minutes, with clean coils and correct airflow. California charge verification needs condenser air between 55 and 115 F dry bulb and return air above 70 F, or you use the weigh-in alternative.
    • Heat pump charge verification. California requires it for heat pumps in every climate zone. An air conditioner in zone 5 or 6 does not need it, but confirm the zone by parcel, because the CEC ZIP table was not read.
    • Pressure references. R-410A saturates at 118.4 psig at 40 F and 317.6 psig at 100 F (CoolProp). R-32 saturates at 121.0 and 325.7 psig at the same temperatures (CoolProp). R-454B runs about 107-112 psig at 40 F and 291-301 psig at 100 F. That is a range from secondary sources, and the spread comes from bubble versus dew points, so use an app set to R-454B. R-454B reads about 5 to 10% below R-410A. R-410A also reads about 131 psig at 45 F and 417 psig at 120 F (interpolated from the BPA chart).
    • Why: weighing gets the amount right. Superheat and subcooling then prove the charge is right for this coil, this airflow and this weather.
  7. Ducts and mastic. Design with Manual D. Fasten joints with screws first, then seal every seam and joint.
    • Use water-based mastic (UL 181 listed), with fiberglass mesh over gaps wider than 1/4 in. UL 181 foil tape also works. Cloth duct tape is not UL 181 approved.
    • Insulate ducts in unconditioned space (R-8 on supply ducts and R-6 on return ducts, per IECC 2009 as cited in the Building America guide).
    • Seal the air handler cabinet, the return platform and the boot-to-drywall gaps, which are the biggest leakers.
    • Test with a duct blaster at 25 Pa. The 2012 IECC allows total leakage of 4 CFM25 per 100 sq ft after construction, and a 2021 jurisdiction form shows the same number. Rough-in limits are 4 with the air handler installed and 3 without.
    • California Title 24 sets leakage as a percent of fan flow. The limit is 5% or less for an entirely new residential duct system, and 6% for ducts in a garage and on the nonresidential form. Duct testing applies above 25 ft of new or replacement duct. For altered systems, airflow verification uses 300 CFM per ton or more (CEC airflow form).
    • Why: leaky ducts waste conditioned air in the attic and pull in dust.
  8. Plenum and return. Build the supply plenum at least as wide as the coil, with turning vanes in sharp transitions. Size the return for low friction.
    • Size filters for about 300 feet per minute of face velocity, which is 1 sq ft per 300 CFM (typical value, check the manufacturer manual). A larger media filter lowers pressure drop.
    • Never draw the return from a garage or mechanical room. Give closed bedrooms a return path, such as jump ducts or transfer grilles.
    • Aim for total external static pressure of 0.5 in. w.c. or less, and expect trouble at 0.8 or higher.
    • Why: a starved return raises static pressure, cuts airflow, and freezes coils.
  9. Condensate. Use a 3/4 in PVC primary drain sloped 1/4 in per foot. The International Mechanical Code minimum is a 1% slope.
    • Add a trap as the manufacturer requires. Never glue the removable trap connection.
    • Install a secondary drain or an auxiliary pan with a float switch, and a vent and cleanout tee downstream of the trap.
    • Where the coil is below the drain, use a condensate pump with a safety switch. Finish with a pour-water test.
    • In Montecito the County storm drain code lists air conditioning condensation as an exempt discharge if it is properly managed and not a nuisance. Sewer connection rules were not confirmed.
    • Why: water damage is among the costliest callbacks, and algae clogs a flat drain within a season or two.
  10. Low-voltage wiring. Use 18-gauge thermostat wire with enough conductors, such as 18/5 or 18/8. Land each wire on the terminal below (the wiring diagram follows this list).
    • R (Rc, Rh): 24 VAC hot from the transformer. Rc is cooling and Rh is heat, jumped if there is one transformer.
    • C: 24 VAC common. Smart thermostats need it.
    • W (W1, W2): heat stages, or auxiliary heat on a heat pump.
    • Y (Y1, Y2): compressor cooling stages. On a heat pump the compressor runs in both modes.
    • G: blower fan.
    • O/B: reversing valve. O energizes in cooling on most brands. B energizes in heating on Rheem and Ruud.
    • Check 24 to 28 VAC between R and C. To isolate the thermostat, jump R to Y for cooling, R to W for heat, and R to G for fan, right at the air handler.
    • Why: one wrong terminal on a heat pump runs it backwards, and a missing C wire makes a smart thermostat reboot.
  11. Commission and document. Work down the checklist, write the readings down, and leave a copy.
    • Unit level, clearances kept, breaker and disconnect sized to MCA and MOCP.
    • Line set sized and insulated; nitrogen hold passed.
    • Evacuation reached target and the decay test passed.
    • Charge weighed in and verified by superheat or subcooling.
    • Static pressure at or under 0.5 in. w.c. (or per the blower data) and airflow about 350-450 CFM per ton. California requires at least 350.
    • Cooling temperature split about 16-22 F (typical value, check the manufacturer manual). Heat rise within the nameplate range.
    • Furnace: manifold pressure, gas inlet pressure, flame microamps and a CO test. Trane lists natural gas manifold at 3.3-3.5 in. w.c. and inlet 4.5 minimum to 14.0 maximum. Read the nameplate for your unit.
    • Condensate: pour-water test and float switch test.
    • Thermostat set up (O/B, stages, balance point) and 24 V verified.
    • Duct leakage tested, filters in.
    • Customer walkthrough, warranty registration.
    • Permit finaled, and the proof of permit kept for the County record and for a 3CE rebate (Montecito).
    • Why: the readings prove the job and protect you if the system fails later.
Startup checks run in order and each one must pass before the nextNitrogenholdEvacuateto a deep vacuumChargethe systemAirflow andstatic pressureTemperaturesplit and riseFurnace gasand COCondensatedrainThermostatsetupDocumentationand photosOut of range at any step: fix it and repeat that step
Startup and commissioning order

Read the top row left to right, then the bottom row right to left. A reading that is out of range sends you back to repeat that step.

Manufacturer values for the nitrogen test, evacuation and add-on charge. These differ by brand and model, so use the manufacturer's installation manual. Each row links to the manual it came from. Where a value was not found, the cell says so. Trane, Lennox, Rheem and Daikin Comfort require a refrigerant detection sensor on their A2L systems.

ManualNitrogen testEvacuationAdd-on, 3/8 in liquidA2L sensor
TraneNameplate maximum, 60 min (optional 150 psig preliminary)350 microns or lower; rise of 500 or less in 1 min and 1,500 or less in 10 min0.47 oz/ftRequired
Carrier 26SCA5About 200 psi, 1 h500 microns; 1,500 or less in 10 min0.60 oz/ft for this R-410A model. The R-454B 38AXQ manual gives 0.54 oz/ft beyond 25 ft.Not checked
Lennox EL18KSLV160 psig, hold not stated500 microns or lower; no rise above 500 in 20 min0.55 oz/ft (the same document also says 0.60)Required
Goodman / Daikin Comfort R-32460 psig, 15 minUnder 500 microns; 10 min isolation0.53 to 0.64 oz/ft by suction size; factory charge covers 15 ft (TP-110 manual)Required
Rheem / Ruud R-454B500 psig maximum, 15 min500 microns or lower, held 15 min0.6 oz/ftRequired
Daikin R-32 mini-split604 psiUnder 500 microns, 1 h0.22 oz/ft beyond 49.25 ft (mini-split line)Not checked
Fujitsu R-410A mini-split600 psig, 24 h500 microns or lower; isolate 1 hNot obtainedNot checked
R and C power the 24 V circuit; W, Y, G and O/B each switch one deviceThermostat terminalsR (Rc, Rh)CW (W1, W2)Y (Y1, Y2)GO/B24 VAC hot24 VAC commonheat callcooling callfan callreversing valve modeTransformer, hot sideTransformer, common sideHeat stage (aux heat on a heat pump)Compressor contactor coilBlower relayReversing valve solenoid (heat pump)Air handler or furnace boardBlue wires are the power pair: expect 24 to 28 VAC between R and C. Grey wires switch one device each.O energizes in cooling on most brands; B energizes in heating on Rheem and Ruud.
Thermostat low-voltage wiring

Wire to this picture and every terminal has one job: R and C carry the 24 V power, and a call on W, Y, G or O/B closes the circuit for heat, the compressor, the blower or the reversing valve.

Rules that changed. Since January 1, 2026, the AIM Act leak-repair rule applies to HFC appliances with 15 lb or more of charge. The old threshold was 50 lb. Residential and light commercial AC and heat pumps are exempt (EPA fact sheet). The old January 1, 2026 install cutoff for R-410A systems built from pre-2025 inventory is superseded by 91 FR 31284, effective July 27, 2026. It removes the installation deadline for qualifying legacy-inventory systems, and only post-2025 R-410A components stay restricted.

Sources: ACCA blog on 500-micron vacuum, Building Science Corporation startup guide, EPA leak guidelines, HVAC School on target superheat, California Energy Commission RA3.2, DOE duct leakage FAQ, Trane gas pressure article, and ServiceMag on the R-410A rule.

Scenes to open. In HVAC Tools in 3D, open Scan, pilot, cut and sleeve: drilling a line set penetration, Cut, ream, swage, bend and pinch copper tube, Make a flare, then torque the nut, Braze a copper joint safely, Nitrogen purge: purge flow versus braze flow, Nitrogen pressure test and temperature drift, Set up the vacuum: pump, large hoses, cores out, Micron gauge: pull down, isolate, watch the rise, Static pressure: supply plus return is the TESP, Seal the duct, then test the leakage and Clear and pump the condensate drain. In HVAC Math in 3D, open Subcooling: how far past condensed, Pressure and temperature go together and Evacuation and pressure test: the method.

Ductwork practice, attics and crawlspaces

Most comfort and efficiency losses hide in the ducts, so how you hang, seal and insulate them matters as much as the equipment.

Why it matters. A Building America guide says duct losses "can be up to 30% or more" when ducts are leaky, poorly insulated and sit in an uninsulated attic or crawlspace. It recommends putting ducts in conditioned space, such as a dropped hallway chase or an insulated, air-sealed crawlspace. Ducts outside conditioned space should be insulated to R-8 for supply and R-6 for return under the 2009 IECC (Building America guide, 2011). Status: confirmed, but the guide is older, so check the current code. California's leakage limits are in the code section.

One sealed air loop: return, blower, trunk, branches, registersReturn grilleFilterAir handlerblower and coilSupply plenumSupply trunkFlex branchRegisterRegisterRegister12341Seal every joint and seam with UL 181 mastic2Support flex duct every 4 ft or closer, and keep it taut3Seal each boot to the finished ceiling or floor4Outside conditioned space, insulate: R-8 supply, R-6 return (IECC 2009)
Duct loop layout

The four numbered checks apply along the whole loop: seal joints and boots, support the flex, and insulate wherever ducts leave the conditioned space.

Flex duct practice

PracticeThe number or ruleStatus
SupportSupports no more than 4 ft apart. Vertical runs supported every 6 ft at least. Straps at least 1.5 in wide. Saddle supports wider than 5.5 in.Confirmed (PNNL, citing the ADC standard 5th ed. and ICC-ES AC 284)
Sag limitThe sources disagree. PNNL says no more than 1/2 in of sag per foot between supports. HVAC School says 1/2 in per 4 ft, and a reader flagged the mismatch. ACCA says Manual D assumes no more than 4% sag, which is a 10 ft piece spanning 9.6 ft. Use the strictest and check the duct maker.Conflict. Which one governs is unconfirmed (HVAC School, ACCA)
StretchPull a 25 ft section fully extended for one minute before installing, and cut off the extra 2 to 6 ft instead of using all of it.Confirmed as quoted (HVAC School)
CompressionThe ADC figure quoted by HVAC School: 30% compression can mean four times the air resistance. ACCA says the extra compression could need a duct two sizes larger.Confirmed as quoted (both pages)
SealingSeal connections with mastic and let the inner liner dry before pulling insulation over it. Seal the boot or can to the finished floor or ceiling before the grille goes on.Confirmed (HVAC School)

Attics and crawlspaces

TopicWhat to doStatus
HeatCal/OSHA's indoor heat rule applies at 82 F, with full requirements at 87 F, or at 82 F with heat-restrictive clothing or high radiant heat. Water must be supplied at one quart per employee per hour if it is not plumbed. New workers are closely observed for 14 days.Confirmed (8 CCR 3396). Whether an attic counts as an indoor work area is unconfirmed, so follow your employer's heat plan
AccessCITY OF SANTA BARBARA ONLY: the City's furnace sheet asks for 30 x 22 x 30 in attic access and a 30 x 30 in service space. Montecito is under the County, which was not confirmed to use that sheet, so ask County Building and Safety.City sheet confirmed (4/12/2018, see the code section); County requirement unconfirmed
Old materialsDuct wrap, flue pipe and pre-1978 paint can hold asbestos or lead. Stop and test before you disturb them.Confirmed (safety table)
CondensateWhere the unit sits over finished space, add a secondary pan or drain with a float switch. Whether the code requires it at a given address is unconfirmed, so check the adopted code.Practice-based
Footing and lightStep only on framing, never on drywall or duct. Carry a headlamp, and tell someone where you are working.Practice-based

Sizing and design mistakes

MistakeWhat goes wrongStatus
Sizing from a rule of thumb or the old unitThe system ends up oversized. The guide says to use ACCA Manuals J, S and D.Confirmed (Building America guide)
Oversized equipmentIt cycles too often, giving less comfort and a shorter life.Confirmed (ENERGY STAR)
Reusing old ducts uncheckedCheck size, balanced pressures and return airflow before you reuse them.Confirmed (Building America guide)
Heat pump on furnace ductsCooler supply air (80 to 115 F) may need bigger ducts.Confirmed (Building America guide)
Skipping airflow and charge checksPoor airflow cuts efficiency, raises bills and leaves the air overly damp.Confirmed (ENERGY STAR)

A2L refrigerants on the job: leak sensors and mitigation

On an A2L system the factory leak sensor is a safety device, so you wire it, test it and never bypass it.

A refrigerant detection system (RDS) is a sensor plus a control board that reacts to a leak. ACHR News describes how three makers build it (ACHR News, 2024-09-06).

TopicWhat to knowStatus
Why it existsUL 60335-2-40 calls for an RDS on new residential and light commercial ducted split systems, generally those with more than 4 lb of refrigerant.Confirmed (ACHR News)
Where the sensor sitsLow in the indoor coil section, typically at the drain pan, because A2L vapor is heavier than air and pools low.Confirmed (ACHR News)
Sensor lifeCarrier and Trane design it to last the life of the unit, and Trane needs no calibration. Daikin's can be replaced in the field.Confirmed (ACHR News)
If the sensor or power failsCarrier defaults to its dissipation cycle on a sensor failure, and removes thermostat calls on a power failure. Daikin shuts the system down on either.Confirmed (ACHR News)
MarkingsTrane puts red markings on service ports and line sets to identify A2L units.Confirmed (ACHR News)
Trip levelThe concentration that trips the sensor is not given in that article.Unconfirmed: typical value, check the manufacturer manual or code
California codeThe 2025 California Mechanical Code requires A2L comfort systems to meet ASHRAE 15 and 15.2 (2022 editions) and to be listed to UL 60335-2-40.Confirmed (LADBS bulletin, revised 2026-01-01)
Which makers require itTrane, Lennox, Rheem and Daikin Comfort manuals require a refrigerant detection system with the unit. The Carrier manual was not checked for it.Confirmed (manufacturer table in Installation)
Your jobWire the sensor and board as the manual shows, test the response, and never jumper it out. Note the test in your commissioning record.Practice-based. The test method is in each manual
A detected leak starts the blower and stops cooling until the air clearsSensor sees refrigerant above its thresholdControl board overrides the thermostat callIndoor blower runs to spread the refrigerantCooling is stoppedCompressor off, or thermostat calls blockedSensor readsclear?yesnoNormal operation returnsCarrier runs the blower a few more minutesSensor or power failureCarrier: runs the dissipation cycleDaikin: the system shuts downAlertsLED flash codes or a thermostat notice;Carrier also tells the dealerWhat stops depends on the makerCarrier: heating and cooling blockedDaikin, Trane: compressor offTrane: furnace and electric heat keep running
A2L leak response flow

A sensor trip turns the blower on and stops cooling, and the system stays that way until the sensor reads clear.

Diagnostics: the top 25 failures

These are the 25 service calls you will see most. Numbers marked "typical value, check the manufacturer manual" were not confirmed against a manual. The nameplate and the manual always win.

Local rules when a diagnosis ends in a replacement. In Montecito the County Code exempts only a swap of component parts, such as a capacitor, contactor or motor. Replacing a whole condenser, furnace or air handler needs a County permit before the work, and moving a condenser can need a written Director determination. Tell the customer that the permit comes first and that the County fee line for HVAC is unconfirmed. See Montecito and Santa Barbara: your local rules.

The master routine (use it on every call)

  1. Safety first. Lock out and tag the power, discharge capacitors, and wear PPE. Use regulated nitrogen only for pressure tests. A2L refrigerants (R-454B, R-32) are mildly flammable, so ventilate and remove ignition sources.
  2. Airflow before anything else. Check the filter, the blower wheel, the coil face, the registers, and total external static pressure (design 0.5 in. w.c. or less, typical value, check the nameplate).
  3. Electrical next. Measure 24 VAC at the control, line voltage at the disconnect, capacitor microfarads, and amp draw against the nameplate.
  4. Refrigerant last. Only after airflow and electrical are proven good. Run 10 to 15 minutes, then read superheat or subcooling and compare with the manufacturer chart.
  5. Document your readings. Write down before and after numbers, outdoor and indoor temperatures, and the part you replaced. Then ask why the part failed.

No-cool decision tree

No cool: prove the blower, the outdoor unit and the airflow before suspecting refrigerantyesyesyesyesnonononoDoes the indoor blower run?Thermostat set to cool, fan onDoes the outdoor unit run?Condenser fan and compressor both startIs the airflow good?Filter and coil clean, static 0.5 in. w.c. or lessDo superheat or subcooling match?After 10 to 15 minutes, against the chartThe equipment is workingLook at the house: load, ducts, sizingCheck 24 VAC from R to C, the 24 V fuse and thethermostat wiring, then the blower capacitor andmotor. Table items 18, 24, 12 and 16.Check 24-28 VAC at the contactor coil, then thecapacitor, contactor and breaker. Never upsizethe breaker. Table items 1, 9, 10 and 8.Fix airflow before touching refrigerant: filter,blower wheel, coil face, registers, restrictions.Table items 2 and 6.Dirty condenser, low charge or a restriction. Findthe leak before adding any, and never vent it.Table items 2 and 7.
No-cool decision tree

Answer the four questions top to bottom and stop at the first no. Each no names the cause to test first and the table rows that cover it.

No-heat decision tree

No heat: prove the 24 V call, then follow the furnace sequence step by stepyesyesyesyesyesnononononoIs 24 VAC present, R to C?Thermostat is calling for heatIs it a gas furnace?Not a heat pumpDoes the inducer start?And the pressure switch closesDoes the igniter glow?Then the burners lightDoes the flame stay lit?And the blower starts after its delayThe furnace is runningCheck temperature rise, then a CO testDead batteries, a loose or broken wire, a missing Cwire, or a blown 24 V fuse. Find the short first.Table items 24 and 18.Heat pump: check the O/B setup, 24 VAC at thereversing valve solenoid, then the defrost sensorand board. Table items 4, 21 and 23.Inducer motor or pressure switch fault, or an openlimit or rollout: read the board LED code.Table items 25, 14, 20 and 13.Failed igniter, no 120 V at its plug, or no 24 V atthe gas valve during the trial. Handle by the base.Table items 19 and 3.Dirty flame sensor first, then flame rollout or alimit trip from poor airflow. Never jump a safety.Table items 15, 13 and 20.
No-heat decision tree

Prove the 24 V call first. Split off the heat pump at question two. Then follow the furnace sequence in order, because the first step that fails is the fault.

Read this before the table

The top 25 table

#SymptomMost likely cause firstTest and expected readingFix
1Outdoor unit silent, indoor blower runsFailed capacitor, then contactor, then breaker or safety switch24-28 VAC at contactor coil. Line voltage 208-250 V. Less than 2 V drop across closed contacts. Capacitor within +/-6% (fan) or +/-10% (start)Replace with exact-rated part. Check amps against RLA. Find why it failed
2Runs but warm air, poor coolingLow airflow or dirty coil, then low charge, then dirty condenserStatic 0.5 in. w.c. or less. Supply/return split 16-22 F (typical value, check manual). Superheat or subcooling per chartFix airflow first. If leak: repair, new drier, evacuate to 500 microns, weigh in
3Gas furnace will not ignite or locks outDirty flame sensor, then igniter, then pressure switchRead board LED code. Watch sequence: inducer, switch closes, igniter glows, valve opens. Igniter continuity; SiC amps 4.75 A or lessClean sensor, replace igniter by its base, fix gas, switch or vent
4No heat from heat pumpThermostat O/B setup wrong, then reversing valve, then defrost control24 V at O or B terminal in the right mode. Warm suction line with small pressure split means valve passing. Defrost sensor ohms vs chartCorrect setup. Replace solenoid or valve. Replace defrost parts
5Short cyclingOversized equipment, then dirty filter or coil tripping safety, then low chargeLog cycle lengths. Read furnace limit code. Check AC pressure switches. Temperature rise within nameplate range (typically 35-65 F)Fix airflow and charge. Consider staged or variable speed. Add 3-5 minute delay
6Frozen evaporator coilDirty filter, coil or slow blower, then low charge, then closed registersThaw first (1-3 hours, fan on). Then static and about 400 CFM per ton (typical value). Low suction pressure after 15 minFix airflow, then charge. Clean coil. Check metering device
7High head pressureDirty condenser, then failed fan motor or capacitor, then overchargeCondensing temp about 30 F over ambient (typical value, varies by brand). Fan RPM and capacitor uF. High subcooling plus high head means overcharge or restrictionClean coil, replace fan or capacitor, recover and weigh in charge
8Tripped breakerGrounded compressor, then failed start capacitor or locked rotor, then low voltageLock out. Windings to ground over 1 megohm (many want 10). C-R plus C-S equals S-R. Running amps at or below RLAReplace grounded part. Never upsize the breaker
9Run or start capacitor failedAge and heat, then voltage surgesDischarge, then measure uF: within +/-6% of label (fan/dual). Bulged or leaking means replaceSame uF, equal or higher VAC rating. Check motor amps
10Contactor failurePitted contacts, then open coil, then low voltage24-28 VAC at coil. Coil about 10-40 ohm (typical value, check manual). Under 2 V drop across closed contactsReplace with equal pole and amp rating. Warn that single-pole leaves L2 live
11Compressor failureSeized or locked rotor, then open or grounded winding, then acid burnoutWinding ohms and ground check (over 1 megohm). High start amps with good capacitor means seizedReplace compressor and drier, flush if burnt, evacuate to 500 microns, weigh in
12PSC blower motor failureFailed run capacitor, then worn bearings, then open windingCapacitor uF first. Winding ohms per label. Amps vs FLA. Shaft spins smooth by handReplace capacitor or motor. Clean the wheel
13Flame rollout tripsCracked heat exchanger, then blocked vent, then low combustion airInspect exchanger with camera. Manifold pressure. CO in flue under 100 ppm air-free (typical value, check manual). Vent and trapFix the cause first. Replace exchanger or furnace if cracked
14Pressure switch faultBlocked vent or intake, then clogged tube or condensate, then bad switchManometer: closes near its printed rating (roughly -0.20 to -1.0 in. w.c.). Continuity with inducer runningClear hose and trap. Replace inducer or switch
15Dirty or failed flame sensorOxide coating, then poor ground, then cracked insulatorFlame current about 0.5-7.0 microamps DC (one brand; 0.5 is the minimum). Check your control manualClean with fine abrasive pad. Clean ground screw. Replace if cracked
16ECM motor faultModule failure, then wrong program, then no control signal120/240 V at power plug. 24 V signal at control plug. Shaft rough by hand means motorReplace module or motor. Use the like model. Confirm power first
17Drain clog, condensate overflowAlgae in trap, then missing trap or vent, then pan slopeBlow out with nitrogen or wet vac. Slope 1/4 in. per footClear it. Add cleanout tee, vent, float switch, pan treatment
18Blown 24 V fuse, dead transformerShort in thermostat wire, then shorted contactor coil, then new accessoryFuse near 0 ohm (OL is blown). Secondary 24-28 VAC no load. Primary voltage presentFind the short first. Same-amp fuse (often 3 A). Never a bigger fuse
19Igniter failureCracked or aged element, then open element, then burnt plugAbout 120 VAC at plug during warm-up. SiC cold ohms 40-75 to 45-400 by model. Amps 4.75 A or less. Line 108-132 VExact OEM igniter, handled by the base. Replace burnt pigtail
20Limit switch overheatingDirty filter or closed registers, then dirty blower or weak motor, then duct restrictionRead which limit is open. Temperature rise within nameplate range. Static 0.5 in. w.c. or less; over 0.8 is a restriction (typical values)Restore airflow. Replace limit only after proving airflow is good
21Reversing valve stuckThermostat O/B setting, then failed solenoid, then no 24 V to solenoid24 VAC at solenoid when called. Coil roughly 100-1,000 ohm (typical value, check coil data). OL or 0 ohm is badFix wiring or setup. Replace solenoid. Valve swap: nitrogen purge, evacuate to 500 microns
22TXV failurePoor bulb contact or insulation, then lost bulb charge, then plugged screenBulb clean, strapped, horizontal run, 4 or 8 o'clock, insulated. Subcooling in nameplate range. On subcooling method, superheat 4-25 F (CEC)Fix and insulate the bulb. Replace TXV and drier if bad. Match refrigerant and tonnage
23Defrost control failureBad defrost sensor, then bad board or timer setting, then dirty coil or low airflowSensor ohms vs chart (many are 10k at 77 F, typical value). Ice-water reading should match chart. Force-test per manualReplace sensor or board. Clear ice and drains. Set timer per manual
24Thermostat or wiring faultDead batteries, then loose or broken wire, then missing C wire24-28 VAC R to C. Jumper R-G, R-Y, R-W at the air handler. Continuity per wireRepair wire. Use spare conductor for C. Replace thermostat last
25Inducer motor failureWorn bearings, then failed capacitor, then open winding115-125 V or 208-240 V per nameplate at plug during call. Wheel spins free. Winding ohms and capacitorExact OEM inducer assembly. Fix condensate path. Reseal vent

Master secrets and common mistakes

Scenes to open. In HVAC Tools in 3D, open Read the gauges: pressure to saturation temperature, Combustion analyzer: air-free CO, O2 and stack temperature, Lock out, then prove it is dead: tester, meter and 24 V, Clamp meter: amps against the nameplate, Capacitor, megohm and burnout checks, Static pressure: supply plus return is the TESP, Measure airflow: pitot, anemometer and flow hood, Delta T: supply and return temperature and Clear and pump the condensate drain. In HVAC Math in 3D, open Airflow per ton and the temperature split, Static pressure: what the blower pushes against, Superheat: how far past boiling, Subcooling: how far past condensed and Is the run capacitor still good?.

Coastal air, heat waves and the work day

Salt air corrodes coils and cabinets, and heat waves put you in the attic at the worst hour. This section covers both for Montecito and Santa Barbara work, with the local pad, fire, flood and noise rules that bite on outdoor units.

TopicWhat to knowStatus
Salt corrosionCarrier says salt can travel as far as 2 miles inland, and gives no single safe distance. Its coastal models carry a 5-year parts warranty against seacoast corrosion. These are Carrier's own claims.Confirmed (Carrier coastal guide)
Pre-season tune-upRinse coils with fresh water, check cabinet paint and fasteners, and clear the drain before the first hot week.Practice-based
Outdoor heat ruleCal/OSHA outdoor heat rules (8 CCR 3395) require shade when it is above 80 F. High-heat procedures start at 95 F or more.Confirmed (Cal/OSHA heat illness page)
Indoor heat ruleA heat wave under 8 CCR 3396 means a predicted high of at least 80 F and at least 10 F above the average high of the previous 5 days.Confirmed (8 CCR 3396)
Design dayManual J sizes for a 1% design temperature, so a heat wave can exceed what the system was sized for. See the design-temps scene in the math page.Practice-based
Work-day planStart attic work early, drink water on a schedule, and keep a second person within earshot.Practice-based
Setting the outdoor unit (Montecito)Use coated coils and stainless or powder-coated fasteners near the ocean. Set the unit on a raised, non-combustible pad, because County floodplain rules want equipment located to keep water out and Montecito Fire's Zone 0 bars items likely to be ignited by embers within 5 ft of the house. Keep wood pads, plastic covers, combustible screens and mulch away from it.Pad and coating advice is practice-based. Flood and Zone 0 rules are confirmed in the local rules section; whether they reach a like-for-like swap is unconfirmed
Screening and noise (Montecito)The Montecito Architectural Guidelines say condensers should be located or buffered, and outside mechanical equipment should be architecturally integrated. Inside Zone 0 a combustible screen is likely to fail the ember rule (our reading, not stated for equipment). Get a written Director determination before you move a condenser or run a visible line set.Guidelines confirmed; whether design review applies to a given swap is unconfirmed

Code, licensing and permits (California)

Three rules decide whether a job is legal: your license, your refrigerant certification, and the Title 24 energy code. Facts below link to the page they came from. Items marked unconfirmed could not be checked.

TopicWhat it saysStatus
EPA 608Four types: I, II, III and Universal. The certification does not expire. The Universal core exam must be proctored.Confirmed (EPA)
608 pass mark70% is the passing score (40 CFR 82 Appendix D). A small appliance holds 5 lb or less of refrigerant. Records are kept 3 years.Confirmed (eCFR)
Venting penaltyClean Air Act maximum is $124,426 per violation for penalties assessed on or after Jan 8, 2025.Confirmed (law.cornell.edu)
HFC phasedown90% in 2022-23, 60% in 2024-28, 30% in 2029-33, 20% in 2034-35, 15% from 2036.Confirmed (EPA)
R-410A install deadlineThe Jan 1, 2026 cutoff for pre-2025 inventory is superseded by 91 FR 31284 (effective July 27, 2026), which removes the install deadline for qualifying legacy-inventory systems.Confirmed (Federal Register)
California refrigerant limitGWP under 750 for ducted central AC and heat pumps, and mini and multi-splits, from Jan 1, 2025.Confirmed (CARB)
Leak repairApplies to appliances with 15 lb or more of HFC charge. Residential AC and heat pumps are exempt.Confirmed (EPA)
C-20 licenseNeeds 4 years of journey-level experience in the last 10, trade and law exams, fingerprints, a $25,000 contractor bond and a $25,000 qualifier bond.Confirmed (CSLB)
CSLB fees$450 application, $200 initial fee for a sole owner ($350 otherwise), $450 renewal every 2 years.Confirmed (CSLB)
Unlicensed work limitThe minor-work threshold rose from $500 to $1,000 on Jan 1, 2025 under AB 2622, not SB 607. The $1,000 exemption is in B&P 7048 and applies only if no building permit is required.Confirmed (CSLB)
2025 codesThe 2025 Energy, Mechanical and Electrical codes take effect Jan 1, 2026.Confirmed (BSC)
Which NEC edition the 2025 California Electrical Code is based onNot stated on any page fetched.Unconfirmed
Attic access and drain slope in the Mechanical CodeCITY OF SANTA BARBARA ONLY: the City sheet (4/12/2018) asks for attic access of 30 x 22 x 30 in. minimum and a 30 x 30 in. service space. It is not a County rule for Montecito. Drain slope of 1/8 in. per ft is a typical value, check the code.City-only attic access confirmed from an older City sheet (City); drain slope unconfirmed
Home improvement contract numbersWritten contract when the price is over $500, which is the coverage threshold in B&P 7159. Down payment capped at $1,000 or 10% of the price, whichever is less. Three business days to cancel.Confirmed (CSLB guide)

Title 24 HERS verification. A third-party rater tests duct leakage, airflow, fan watts and refrigerant charge.

TestRequirementStatus
When duct testing appliesMore than 25 ft of new or replacement ductConfirmed (gocodebook, code publisher)
New duct system leakage5% or lessConfirmed: 5% for an entirely new residential duct system. 6% applies to ducts in a garage and on the nonresidential form. Source: (CEC form)
Altered duct leakage10% total, or 7% to outside, or seal every accessible leakConfirmed (CEC form)
Airflow, new system350 CFM per ton or moreConfirmed (CEC airflow form)
Airflow, altered system300 CFM per ton or more (250 for small-duct high-velocity)Confirmed (CEC airflow form)
Fan efficacy0.45 W/CFM for gas furnace air handlers, 0.58 W/CFM for others, 0.62 for small-ductConfirmed (CEC fan efficacy form)
Refrigerant chargeTriggered by replacing the compressor, coil, metering device or refrigerant piping. Weigh-in is an alternative.Confirmed (CEC charge form)

Check this for Montecito and Santa Barbara. The Energy Commission lists refrigerant charge verification for air conditioners only in climate zones 2 and 8 to 15, and for heat pumps in all zones (CEC). The CEC Building Climate Zones layer puts Montecito's coast and valley, the City of Santa Barbara, Carpinteria, Summerland and Goleta in zone 6, and upper Montecito above about 34.455 N in zone 5. Neither is in zones 2 or 8 to 15, so a heat pump needs charge verification and an air conditioner does not. The CEC ZIP table was not read, so confirm the zone by parcel with the CEC lookup; a 2016 CAPCOA table lists 93108 as zone 8, which conflicts with the CEC layer, and in zone 8 an air conditioner would need it.

Permits. Mechanical permits plus Title 24 forms with HERS testing before final are the general process. In Montecito the permit comes from the County of Santa Barbara Planning and Development, not the City. A whole-unit replacement needs a County permit, and the County fee schedule has no air conditioner, heat pump or change-out line, so quote the closest lines and confirm with the County (see the section Montecito and Santa Barbara: your local rules). CITY OF SANTA BARBARA ONLY: the FY26 fee schedule (effective 2025-09-01) lists $627 for a furnace new or replacement permit and $315 for a wall heater, with no separate line for an air conditioner or heat pump (City fee schedule). Like-for-like replacements can use the City's On-Demand portal, and Santa Barbara Clean Energy covers up to $820 of heat pump permit fees (City sustainability page). The City's HVAC permit checklist says a HERS duct leakage test is required when a furnace is replaced and the ducts stay, and it lists a 53 dBA condenser limit at the adjacent residential property line and 5 ft side and 10 ft front setbacks. Those are City figures: do not quote them for a Montecito job. The Coastal Zone exemption for HVAC was not confirmed.

Montecito, Santa Barbara and coastal considerations

Rows marked Unconfirmed or practice-based were not confirmed against a fetched county, city or manufacturer page, so check them locally before you quote them to a customer. The confirmed County rules for permits, design review, noise, fire and flood are in the section Montecito and Santa Barbara: your local rules.

TopicWhat to doBasis
Salt-air corrosionNear the coast, specify coated coils or marine-grade protection for outdoor units.Practice-based, no manufacturer source fetched.
Coil warrantyRead the manufacturer's terms: coastal corrosion can void a coil warranty when the coil is not coated.Practice-based, unconfirmed.
Coastal Zone permitsNot confirmed as exempt. Article II exempts repair and maintenance that does not enlarge, with no HVAC or like-for-like wording, and the Montecito Coastal Zone boundary is unconfirmed. Ask County Planning.Unconfirmed.
Who issues the permitMontecito is unincorporated and falls under County of Santa Barbara Planning and Development. The City of Santa Barbara has its own Community Development department, and Carpinteria and Goleta have their own building departments.Confirmed from the County Building and Safety page; the permit path is in the local rules section
Noise and setbacksMontecito: County Code Chapter 40 quiet hours and the Montecito zoning setbacks apply by parcel, and no equipment noise limit was found. CITY OF SANTA BARBARA ONLY: 53 dBA at the adjacent residential property line and 5 ft side and 10 ft front setbacks.Unconfirmed for Montecito; City figures confirmed (see the local rules section).
Climate zone 5 or 6Montecito's coast and valley, the City, Carpinteria, Summerland and Goleta are in zone 6, and upper Montecito above about 34.455 N is in zone 5. Charge verification applies to heat pumps in every zone but to air conditioners only in zones 2 and 8 to 15, so a heat pump needs it here and an air conditioner does not. Confirm the zone by parcel.Confirmed (CEC).
Heat pumpsIn these mild-marine zones heat pumps are the prescriptive baseline for new single-family homes.Unconfirmed.
Older homesMany Santa Barbara and Montecito homes predate 1980. Test duct wrap, flue pipe and floor tile before you disturb them.Lead and asbestos rules are confirmed in the Safety table.

Scenes to open: In HVAC Math in 3D, open COP, EER and HSPF2: heat for every watt, Whole-house ventilation, ASHRAE 62.2 and California Title 24: airflow, fan watts, leakage.

Business: contracts, liens and pricing

A job is not finished until you are paid, and in California the paperwork protects you as much as the customer. This section gives the sourced rules. Hours, prices and margins are not sourced anywhere and are marked as such.

Home improvement contracts (B&P 7159).

Preliminary notice and liens (Civil Code 8200; deadlines from the CSLB guide).

RuleTime limit
Subcontractors and suppliers send a preliminary noticeWithin 20 days of first furnishing (Civil Code 8204)
Original contractor records a lien90 days after completion, or 60 days after a recorded notice of completion (Civil Code 8412)
Others record a lien90 days after completion, or 30 days after a recorded notice (Civil Code 8414)
File suit to forecloseWithin 90 days of recording the lien (Civil Code 8460)

A contractor working directly for the owner does not send a preliminary notice but must give the owner the statutory notice. These deadlines come from the CSLB homeowner guide to mechanics liens, which cites the 2016 code edition. Confirm them against the Civil Code or a construction attorney before relying on them.

Warranties. California allows suit for latent construction defects for 10 years from substantial completion (CCP 337.15). Manufacturer warranties vary by brand and by whether the unit is registered. Read each one.

Pricing math you can trust. Margin is profit divided by price. Markup is profit divided by cost. A 40% margin needs a 66.7% markup, so adding 40% to your cost gives only a 28.6% margin. Use the margin formula to set prices:

Price=Cost/(1−Margin)Price = Cost / (1 - Margin)

Labor hours per job, overhead and burden percentages, price ranges for a system and the HERS test fee are rules of thumb, not sourced. Build your own numbers from your last ten jobs rather than copying anyone else's.

Quoting in Montecito. Quote the County permit as the closest lines on the County fee schedule (heating appliance, cooling unit add-on, furnace or air-handling unit, plus a $313 hourly plan check, a $156 issuance fee and 6.00% and 3.70% surcharges) and say the County sets the final fee. Never carry over the City's $627 furnace figure. A whole-unit replacement needs a County permit, so the $1,000 unlicensed-work exemption in B&P 7048 does not apply. Add schedule time for a written Director determination and, if design review applies, a Board of Architectural Review meeting (every other Thursday, applications due three weeks before). Tell the customer a rebate needs proof of permit and may not apply. See Montecito and Santa Barbara: your local rules.

Customers, upsell ethics, documentation and warranty registration

A trusted tech sells what the house needs, writes down what was done, and registers the equipment. The rows below cover most of it.

TopicWhat to knowStatus
High-pressure salesThe CSLB "Don't Be Fooled" guidance warns about high-pressure sales, bait and switch, free inspections used as a hook, and down payments above 10% or $1,000.Confirmed (CSLB consumer education)
Quality installENERGY STAR quality installation covers sizing, airflow, charge and a duct evaluation. ACCA Quality Assured is a matching contractor program.Confirmed (ACCA)
Warranty registrationTrane says to register within 60 days. A registered limited warranty is "in most cases 10 years" against "typically five years" unregistered. It covers parts only. Trane warns: never assume your dealer is registering your product.Confirmed (Trane warranty page)
Refrigerant recordsEPA requires 3 years of service records for appliances that fall under its leak-repair rules.Confirmed (EPA leak-repair fact sheet)
Photos and paperworkTake before and after photos of the nameplate, gauges, readings and ducts. Leave the customer a one-page summary with the numbers.Practice-based
Upsell testRecommend a repair or upgrade only when you can show a reading or a photo that proves the need.Practice-based

California rebates and incentives for heat pumps, as of 2026-10-28

Most heat pump money is now reserved or expired, so check the live pages before you promise a customer anything.

ProgramWhat it paidStatus as of 2026-10-28Source
Federal 25C tax creditUp to $2,000 for a heat pumpExpired 12/31/2025Trane
HEEHRA (home electrification rebate)Up to $8,000 below 80% of area median income, up to $4,000 at 80 to 150%. Amounts stack.Statewide funds fully reserved as of 2026-02-24. Needs a TECH-certified, HEEHRA-trained contractor.TECH Clean California
TECH heat pump incentiveUp to $1,500 for a heat pump HVACSingle-family heat pump incentives reserved statewide as of 2025-11-14TECH single-family page
3CE Electrify Your Home (Montecito and other unincorporated County addresses on a 3CE account)Heat pump HVAC rebate. The 2026-27 dollar amounts are in an unreadable image; the 2025 flyer showed $2,000, or $3,000 income-qualified, and may be supersededInstalls 2026-08-01 to 2027-09-30, apply by 2027-09-30, electric-only, proof of permit required, first come first served3CE Electrify Your Home
Santa Barbara Clean Energy permit help (CITY OF SANTA BARBARA ONLY)Covers up to $820 of Mechanical Express Permit fees for qualifying heat pump HVAC replacementsCheck current termsUnconfirmed: check the SBCE site
Santa Barbara HEAP (CITY OF SANTA BARBARA ONLY)Heat pump water heater up to $3,500, electrical work up to $4,000Page dated 2025-01, check currentUnconfirmed: check the program page

To join TECH as a contractor, use the TECH Contractor Enrollment form or email TECH.contractor@energy-solution.com. Never promise a rebate in a quote. Say "may qualify" and point to the live page.

Day 1 to master: a staged course

This course takes you from your first day to a service and design master in nine stages. Move to the next stage only when you can do the practice alone and answer the "explain" line without notes. The time per stage is a practice-based suggestion for someone working at it most days, not a requirement from any code or license. Each stage links to scenes by name in HVAC Math in 3D (35 scenes) and HVAC Tools in 3D (25 scenes, 70 tools; set its Level menu to Beginner for the first stages).

Your first-day tool kit

Buy these first. Each has a scene or tool entry in HVAC Tools in 3D.

Stage 0, day 1: safety and names

Stage 1, week 1: how the system works

Stage 2, weeks 2 to 3: electricity and measuring

Stage 3, weeks 4 to 6: airflow, ducts and static pressure

Stage 4, weeks 7 to 10: copper, nitrogen and vacuum

Stage 5, months 3 to 4: charge and service

Stage 6, months 5 to 6: gas, combustion and furnaces

Stage 7, months 7 to 12: design and code

Stage 8, year 2 and on: master and contractor

Common mistakes of beginners

Self-check questions

Cover the answer column and try each question aloud.

#QuestionAnswer
1Name the four parts of the refrigerant loop in order.Compressor, condenser, metering device, evaporator.
2What do you check first on a no-cool call?Airflow: filter, blower wheel, coil face, registers and total external static pressure.
3What is the sensible heat formula, and where does 1.08 come from?Q = 1.08 x CFM x temperature change. 1.08 = 60 minutes x 0.075 lb per cubic foot x 0.24 BTU per lb per F.
4Which metering devices use superheat, and which use subcooling?Superheat for fixed-orifice or piston systems. Subcooling for TXV systems.
5At what pressure does R-410A saturate at 40 F and 100 F?118.4 and 317.6 psig (CoolProp).
6Why flow nitrogen while brazing?Without it black scale forms inside the tube and later clogs the metering device and fouls the oil.
7What are the nitrogen test pressure and hold time?It differs by manufacturer (160 to 604 psig, 15 minutes to 24 hours). Use the manufacturer's installation manual.
8What microns do you pull to, and what decay is a pass?500 microns or lower. The decay pass line differs by source, so use the manufacturer's manual.
9Which thermostat terminal calls for the compressor, the blower, heat and the reversing valve?Y, G, W and O/B. R and C are the 24 VAC power pair.
10What voltage do you expect from R to C?24 to 28 VAC.
11How do you discharge a run capacitor?Through a resistor, never a screwdriver.
12What is the flue CO limit for a furnace?400 ppm air-free (ANSI Z21.47).
13What static pressure is the design target?0.5 in. w.c. total external static pressure or less, and trouble at 0.8 or higher (typical values, check the manufacturer manual).
14What airflow does California require per ton?At least 350 CFM per ton for new systems, 300 for altered systems.
15In what order do Manual J, S and D run?Load first, then equipment, then ducts, then verify on site.
16Why is square feet per ton a poor way to size?It ignores how tight and well insulated the house is. Run the load calculation.
17How steep should a condensate drain slope?1/4 in per foot is the usual rule. The International Mechanical Code minimum is 1%.
18At what height does fall protection start, and how far above the landing does a ladder extend?6 ft, and 3 ft above the landing.
19What must you do differently on an A2L system?Use A2L-rated recovery machines, manifolds and leak detectors, remove ignition sources and ventilate.
20What does Title 24 use to limit duct leakage, and what are the two limits?A percent of fan flow: 5% for an entirely new residential duct system, 6% for ducts in a garage and the nonresidential form.

Careers, certifications and training

Only the EPA 608 card is legally required to handle refrigerant. The rest raise pay and trust.

CredentialWhat it isStatus
EPA 608Four types. It does not expire. The Universal core exam must be proctored. No federal A2L certificate was found.Confirmed (EPA)
NATEA nonprofit certification body. Exam details were not fetched.Unconfirmed: typical value, check NATE
HVAC ExcellenceEmployment Ready, Professional Level (verifiable experience) and Master Specialist. Master needs at least 3 years of field experience, a related written certification such as NATE, and a hands-on exam.Confirmed (HVAC Excellence)
ACCAQuality Assurance and Quality Installation credentials, plus EPA 608 and A2L training.Confirmed (ACCA)
CSLB C-20 licenseThe contractor license for HVAC work. Experience requirements are in the code and licensing table above.Confirmed (CSLB C-20)
ApprenticeshipA registered California program runs 5 years. Hours were not stated in the example found. Local Santa Barbara programs were not confirmed.Unconfirmed: typical value, check the program and the state apprenticeship office

Mastery path, glossary and source ledger

The skill ladder. Move up only when you can do the step alone and explain why.

  1. Helper: safety, tools by name, reading a manifold gauge, pulling a filter, cleaning a coil.
  2. Install tech: flare and braze a line set with nitrogen, pressure test, evacuate to a micron gauge, land low-voltage wires.
  3. Service tech: run the diagnostic routine, measure static pressure and temperature split, set charge by superheat and subcooling.
  4. Lead tech: run a load calculation, pick equipment, design and test a duct system, pass a HERS verification.
  5. Contractor: license, estimate, contract, permit, lien notices, warranty.

Practice drills.

Glossary.

TermPlain meaning
A2LA refrigerant safety class: lower toxicity, mildly flammable. R-32 and R-454B are A2L.
ACCAAir Conditioning Contractors of America, the group that publishes Manual J, S and D.
ACH, ACH50Air changes per hour. ACH50 is the result of a blower door test at a 50 pascal pull.
AHRIThe trade institute that certifies equipment ratings and publishes refrigerant safety guidance.
AIM ActThe federal law that phases down HFC refrigerants and sets leak-repair rules.
Air-free COA carbon monoxide reading corrected to what it would be with no extra air in the flue gas.
Air handlerThe indoor cabinet with a blower and evaporator coil when there is no furnace.
ASHRAEThe engineering society that writes ventilation, weather and refrigerant safety standards.
Balance pointThe outdoor temperature at which a heat pump's output just equals the heat the house loses.
BlowerThe fan that moves house air across the coil or heat exchanger and through the ducts.
Blower doorA fan set in a doorway to pull the house to a test pressure and measure its leakage.
BrazingJoining copper with a filler rod melted by a torch. Flow nitrogen through the tube while you do it.
BTU, BTU/hA unit of heat. BTU/h is a rate: how much heat moves per hour.
Bubble point and dew pointFor a blend, the temperature where liquid starts to boil and where vapor starts to condense. Use dew for superheat and bubble for subcooling.
CapacitorStores charge to start or run a motor. Discharge it through a resistor before you touch it.
CECThe California Energy Commission, which writes the Title 24 energy code and its forms.
CFMCubic feet of air per minute.
ChargeThe amount of refrigerant in a system, set by weight and verified by superheat or subcooling.
CMCThe California Mechanical Code, the state code for HVAC installation.
CompressorThe pump that raises refrigerant pressure and temperature.
CondensateWater that drips off a cold coil as moisture leaves the air.
CondenserThe coil that rejects heat to the outdoor air and turns hot gas into liquid.
ContactorA relay that closes the line-voltage circuit to the compressor and condenser fan when the thermostat calls.
COPCoefficient of performance: heat delivered divided by energy used, in the same units.
CSLB C-20The California contractor license classification for heating, ventilation and air conditioning.
C wireThe 24 VAC common. Smart thermostats need it.
Defrost cycleA heat pump briefly runs in reverse to melt ice off the outdoor coil.
Delta T (split)A temperature difference, such as supply versus return air across a coil.
Dew pointThe air temperature at which moisture starts to condense out.
DisconnectThe switch near the outdoor unit that cuts line voltage. Lock it out before service.
DOEThe U.S. Department of Energy.
Drier (filter drier)A canister in the liquid line that traps moisture and debris. Replace it when the system is opened.
Duct blasterA calibrated fan that pressurizes the ducts, usually to 25 Pa, to measure leakage.
ECMElectronically commutated motor: a variable-speed blower motor with its own control module.
EER, EER2Cooling output per watt at fixed conditions. EER2 uses the newer test.
EEVElectronic expansion valve: a metering device driven by a controller.
EnthalpyThe total heat in air, sensible and latent, in BTU per pound of dry air.
EPA 608The federal certification needed to buy or handle refrigerant.
ERV and HRVVentilators that swap stale indoor air for fresh outdoor air and recover part of the heat.
EvacuationPulling a deep vacuum to remove air and moisture before charging.
EvaporatorThe coil that absorbs heat from the indoor air and boils the liquid into gas.
Flame rolloutFlames rolling out of the burner area, usually from a blocked vent or heat exchanger problem. A rollout switch shuts the furnace down.
Flame sensorA rod that proves flame by sensing a tiny current (microamps) through it.
FlareA 45 degree flared tube end that seals against a fitting with a flare nut.
FLA, RLAFull load amps for a motor and rated load amps for a compressor, from the nameplate.
Friction rateThe pressure the duct system can spend per 100 feet of duct, used to size ducts in Manual D.
GrainA unit of moisture weight. There are 7,000 grains in a pound.
GWPGlobal warming potential: how strongly a refrigerant warms the climate compared with carbon dioxide.
HEAP, HEEHRA, TECH, SBCERebate and incentive programs: Santa Barbara HEAP and Santa Barbara Clean Energy (both City only), the federal HEEHRA home electrification rebate, TECH Clean California and 3CE Electrify Your Home (Montecito).
Heat exchangerThe metal passages in a furnace where hot combustion gas heats the house air without mixing with it.
Heat pumpA system with a reversing valve that moves heat in either direction, so it heats or cools.
Heat riseHow much a furnace warms the air passing through it. The nameplate gives the allowed range.
HERSHome Energy Rating System: the third-party test required by Title 24.
HFCHydrofluorocarbon: the refrigerant family that includes R-410A.
Hot surface igniterAn electric element that glows to light the gas. Handle it by the base.
Humidity ratioPounds of water vapor per pound of dry air.
IECCInternational Energy Conservation Code, a model energy code used as a reference for duct insulation.
InducerThe small fan that pulls combustion gas through a furnace and out the vent.
InfiltrationOutdoor air leaking into the house through cracks.
in. w.c.Inches of water column: a small pressure unit used for duct and gas pressure.
LADBSLos Angeles Department of Building and Safety, whose bulletin summarizes the 2025 mechanical code for A2L systems.
Latent heatThe heat carried by moisture. Removing water from air takes energy without changing the temperature.
LFLLower flammability limit: the lowest refrigerant concentration in air that can burn.
Limit switchA safety switch that shuts off the burners if the furnace overheats.
Line setThe pair of copper lines, suction and liquid, joining the outdoor and indoor units.
Liquid lineThe smaller copper line that carries liquid refrigerant to the metering device.
Lockout and tagoutTurning power off, locking the switch and tagging it so nobody turns it back on.
Manifold gauge setGauges and hoses that read refrigerant pressure at the service valves.
Manual J / S / DThe load calculation, equipment selection, and duct design standards from ACCA.
Manual SThe ACCA method for choosing equipment that fits the Manual J load.
Manual DThe ACCA method for sizing ducts to the equipment airflow.
MasticA paste that seals duct seams. Use a UL 181 listed type.
MCA / MOCPMinimum circuit ampacity and maximum overcurrent protection, from the nameplate.
Megohm testA test of very high resistance between a motor winding and ground. Over 1 megohm is the usual minimum.
MERVA filter rating for how well it catches particles. Higher numbers catch more and restrict airflow more.
Metering deviceThe part that drops refrigerant pressure before the evaporator: a TXV, an EEV or a fixed orifice (piston).
MicronA unit for very low pressure. 500 microns is a deep vacuum.
Mini-splitA ductless system: one outdoor unit feeding one or more wall or ceiling heads.
NameplateThe label on a unit with its electrical data, charge and test pressures. It outranks any chart.
NATENorth American Technician Excellence, a nonprofit HVAC certification body.
Nitrogen purgeFlowing dry nitrogen through a line while brazing so the inside does not scale.
OSHAThe federal Occupational Safety and Health Administration. Cal/OSHA is the California version.
PlenumThe sheet metal box that connects the furnace or coil to the main ducts.
Pressure switchA switch on a furnace that proves the inducer is moving air before the igniter and gas are allowed.
PSC motorPermanent split capacitor motor: a single-speed motor that needs a run capacitor.
psig and psiaPounds per square inch gauge and absolute. Absolute equals gauge plus 14.696.
PT chartA table of the boiling temperature for each pressure of a refrigerant.
R-32, R-454BMildly flammable (A2L) refrigerants used in newer equipment.
R-410AThe standard residential refrigerant for years, being replaced in new equipment.
RA3.2The Title 24 reference appendix for refrigerant charge verification.
RDSRefrigerant detection system: the leak sensor and controls on A2L equipment.
Return airHouse air drawn back to the blower.
Reversing valveThe valve that switches a heat pump between heating and cooling.
Saturation temperatureThe temperature at which a refrigerant boils or condenses at a given pressure.
SCFHStandard cubic feet per hour: a gas flow rate corrected to standard conditions, used for nitrogen.
SEER2 / EER2 / HSPF2Efficiency ratings for cooling season, cooling at fixed conditions, and heating season.
Sensible heatThe heat you can measure with a thermometer.
Short cyclingA system turning on and off too often, often from oversizing or a safety tripping.
SHRSensible heat ratio: the sensible share of the total cooling load.
SMACNAThe sheet metal contractors association that publishes duct construction standards.
Static pressureThe resistance the blower pushes against, in inches of water column. Total external static pressure adds supply and return.
SubcoolingHow far the liquid is below its condensing point at the condenser outlet.
Suction lineThe larger, insulated copper line that carries cool vapor back to the compressor.
SuperheatHow far the refrigerant gas is above its boiling point at the evaporator outlet.
Supply airConditioned air delivered to the rooms.
TESPTotal external static pressure: the supply plus return pressure the blower works against.
ThermostatThe control that sends 24 V calls for heat, cooling and fan.
Title 24California's energy code. It sets airflow, fan watts and duct leakage requirements for HVAC.
TonA unit of cooling: 12,000 BTU/h.
TransformerSteps line voltage down to the 24 VAC used by the controls.
Triple evacuationPull a vacuum, break it with nitrogen, pull again, for a wet or contaminated system.
TXVThermostatic expansion valve: a metering device that holds superheat steady and is charged by subcooling.
UL 181The listing for duct sealing products such as mastic and foil tape. Cloth duct tape is not UL 181 approved.
Wet bulbThe temperature a wet thermometer reaches in moving air. It reflects both heat and moisture.

Source ledger. What each part of this guide rests on:

AreaConfirmed from fetched pagesStill unconfirmed or rule of thumb
EPA, CARB, CSLB608 types and 70% pass score (EPA); 5 lb small appliance; 3-year records and the 15 lb leak-repair threshold with its residential exemption (EPA fact sheet); HFC phasedown; R-410A install rule change (91 FR 31284); CARB GWP limit; license bonds and fees (CSLB fees, bond rules); CSLB contract numbers (CSLB guide); CO alarm statute (SB 183); Cal/OSHA lead limit (1532.1) and silica limitR-32 flammability limit; R-454B limit (sources conflict); A2L cylinder markings (one source says required, another says should); leginfo statute pages could not be read, so statute rows rest on republished text
Title 242025 code date; new-duct leakage as a percent of fan flow, 5% for an entirely new residential duct system and 6% for garage ducts and the nonresidential form (CEC form); charge verification by climate zone (CEC); 10% and 7% altered limits; 350 and 300 CFM per ton (CEC airflow form); 0.45 and 0.58 W/CFM (CEC fan efficacy form)Form numbers; NEC edition; leginfo statute pages (not readable); heat pump Manual S limits
Contracts and liensB&P 7159 terms (B&P 7159); B&P 7048; CCP 337.15 (CCP 337.15); lien deadlines (CSLB lien guide) and Civil Code 8204, 8412, 8414 and 8460 from republished textThe leginfo statute pages could not be read, so republished text is secondary
ToolsEPA recovery levels; OSHA CO limits (OSHA); fall rules (OSHA 1926.501); 500-micron target (ACCA blog); manifold pressures; nitrogen cylinder fill (Nippon Sanso)About 114 minor details (hex sizes, pump specs, glove ratings, prices)
MathSuperheat and subcooling from CoolProp; SEER2/HSPF2 definitions; ventilation formula (ACCA 62.2 post); the 1.08, 4.5 and 500 constants re-derivedMost Manual J, S and D tables (paywalled); gas pipe sizing, which is left out on purpose
Install and diagnostics14 of 23 tracked values, plus the manufacturer values for nitrogen test, evacuation decay, add-on charge and A2L sensors (eight manuals)A universal value for nitrogen test, decay limit or add-on charge (none exists: use the manufacturer's manual); Carrier and Mitsubishi A2L sensor rules; heat pump Manual S sizing limits; silicon-nitride igniter ohms
Heat pumps, mini-splits, thermostats, ventilation, water heaters, ventingThe DOE heat pump page, the Building America duct guide, EPA indoor air pages and gocodebook code text, each linked in its own sectionSanta Barbara choice of ERV or HRV; undated DOE pages
A2L on the job and ductworkACHR News 2024-09-06 on leak sensors; the LADBS bulletin on CMC 2025Sensor trip level; makers not checked
Coastal, customers, rebates, careersCarrier coastal guide; Cal/OSHA 3396; Trane warranty page; TECH Clean California; EPA 608NATE exam details; apprenticeship hours; current SBCE and HEAP terms (City only); 3CE 2026-27 dollar amounts
Estimating and pricingNoneAll hours, prices and margins; the County fee line for an air conditioner, heat pump or change-out and the Coastal Zone exemption (the $627 furnace permit is a City of Santa Barbara figure, confirmed for the City only)
Montecito and Santa Barbara local rulesWhich agency issues the permit (County Building and Safety); the County fee schedule effective 2026-07-01 (fee schedule) and its lack of an AC or heat pump line; County Code text from the gocodebook.com republisher (secondary); the Montecito code and Architectural Guidelines; Montecito Fire standards; climate zones from the CEC layer (point queries); 3CE eligibility; City figures confirmed for the City onlyThe items in the open-items list of the local rules section, including the CEC ZIP table, the Coastal Zone parcel boundary, the County HVAC checklist and fee line, whether a condenser needs design review, Montecito vent and ember rules, how County noise rules reach a condenser, and 3CE dollar amounts

The manufacturer table in the Installation section cites the manuals that were fetched. Where this guide and a manual disagree, the manual wins.